CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
55
CGW-MB Control Features
Modbus Communications
Zone Commands
7.19.4 Sending Commands
Send commands through the CGW-MB by writing command values to the appropriate
holding registers. For detailed register mapping information refer to the
section. The following tables display the values representing all the command
types for nodes, points, and zones.
For Panels of All Brands
Table 7.8: Node Commands
Serial
No
Command
value
Holding Register
1
ActivateDeactivateSounder
0x1300 - Activate
Use Zone Holding Register
number
2
ActivateDeactivateSounder
0x1400 - Deactivate
Use Zone Holding Register
number
3
EnableDisableZone
0x0600 - Enable
Use Zone Holding Register
number
4
EnableDisableZone
0x0700 - Disable
Use Zone Holding Register
number
3
SetZoneMode
0x1500
Use Zone Holding Register
number
4
TerminateTest
0x12
Use Zone Holding Register
number
Table 7.7: Zone Command Availability by Panel
General Zones
Logic Zones
Trouble/Release
Zones
Panel Type
Enable/
Disable
Activate/
Deactivate
Enable/
Disable
Activate/
Deactivate
Enable/
Disable
Activate/
Deactivate
AFP-2800
Yes
No
No
No
No
No
AFP-3030
Yes
No
No
No
No
No
N16
Yes
Yes
Yes
No
No
No
NFS-320
Yes
No
No
No
No
No
NFS-640
Yes
No
No
No
No
No
NFS2-640
Yes
No
No
No
No
No
NFS-3030
Yes
No
No
No
No
No
NFS2-3030
Yes
Yes
Yes
No
No
No
XLS 120
Yes
No
No
No
No
No
XLS 140-2
Yes
No
No
No
No
No
XLS 2000
Yes
No
No
No
No
No
XLS 3000
Yes
Yes
Yes
No
No
No
Command
Value
Holding Register
Reset
0x0000
20001
Silence
0x0001
20001