Chapter 4 Explanation of Functions
4 - 139
(6) List of registers
The "R/W" column of the list indicates whether the coils and registers are read-only or readable and
writable.
"R" indicates a read-only coil or register. "R/W" indicates a readable and writable coil or register.
(i) List of coils
Coil No.
Item
R/W
Setting
0000h (Reserved)
-
0001h
Operation command
R/W
1: Run, 0: Stop (valid when A002 = 03)
0002h
Rotation direction command
R/W
1: Reverse rotation, 0: Forward rotation (valid when A002 = 03)
0003h
External trip (EXT)
R/W
1: Trip
0004h
Trip reset (RS)
R/W
1: Reset
0005h (Reserved)
-
0006h (Reserved)
-
0007h
Intelligent input terminal [1]
R/W
1: ON, 0: OFF (*1)
0008h
Intelligent input terminal [2]
R/W
1: ON, 0: OFF (*1)
0009h
Intelligent input terminal [3]
R/W
1: ON, 0: OFF (*1)
000Ah
Intelligent input terminal [4]
R/W
1: ON, 0: OFF (*1)
000Bh
Intelligent input terminal [5]
R/W
1: ON, 0: OFF (*1)
000Ch
Intelligent input terminal [6]
R/W
1: ON, 0: OFF (*1)
000Dh
Intelligent input terminal [7]
R/W
1: ON, 0: OFF (*1)
000E
h
Intelligent input terminal [8]
R/W
1: ON, 0: OFF (*1)
000Fh
Operation status
R
1: Run, 0: Stop (interlocked to "d003")
0010h
Rotation direction
R
1: Reverse rotation, 0: Forward rotation (interlocked to "d003")
0011h
Inverter ready
R
1: Ready, 0: Not ready
0012h Unused
R
0013h
RUN (running)
R
1: Tripping, 0: Normal
0014h
FA1 (constant-speed reached)
R
1: ON, 0: OFF
0015h
FA2 (set frequency overreached)
R
1: ON, 0: OFF
0016h
OL (overload notice advance signal (1))
R
1: ON, 0: OFF
0017h
OD (output deviation for PID control)
R
1: ON, 0: OFF
0018h
AL (alarm signal)
R
1: ON, 0: OFF
0019h
FA3 (set frequency reached)
R
1: ON, 0: OFF
001Ah
OTQ (over-torque)
R
1: ON, 0: OFF
001Bh
IP (instantaneous power failure)
R
1: ON, 0: OFF
001Ch
UV (undervoltage)
R
1: ON, 0: OFF
001Dh
TRQ (torque limited)
R
1: ON, 0: OFF
001Eh
RNT (operation time over)
R
1: ON, 0: OFF
001Fh
ONT (plug-in time over)
R
1: ON, 0: OFF
0020h
THM (thermal alarm signal)
R
1: ON, 0: OFF
0021h (Reserved)
-
0022h (Reserved)
-
0023h (Reserved)
-
0024h (Reserved)
-
0025h (Reserved)
-
0026h
BRK (brake release)
R
1: ON, 0: OFF
0027h
BER (brake error)
R
1: ON, 0: OFF
0028h
ZS (0 Hz detection signal)
R
1: ON, 0: OFF
0029h
DSE (speed deviation maximum)
R
1: ON, 0: OFF
002Ah
POK (positioning completed)
R
1: ON, 0: OFF
002Bh
FA4 (set frequency overreached 2)
R
1: ON, 0: OFF
002Ch
FA5 (set frequency reached 2)
R
1: ON, 0: OFF
002Dh
OL2 (overload notice advance signal
(2))
R
1: ON, 0: OFF
002Eh
Odc: Analog O disconnection detection
-
002Fh OIDc:
Analog
OI
disconnection detection
-
0030h
O2Dc: Analog O2 disconnection
detection
-
0031h (Reserved)
-
0032h
FBV (PID feedback comparison)
R
1: ON, 0: OFF
0033h
NDc (communication train
disconnection)
R
1: ON, 0: OFF
0034h
LOG1 (logical operation result 1)
R
1: ON, 0: OFF