Chapter 4 Explanation of Functions
4 - 32
(2) Curve constant (swelling degree)
Specify the swelling degree of the acceleration curve with reference to the following graphs:
The acceleration or deceleration time may be shortened midway through the acceleration or deceleration
according to the S-curve pattern.
If the LAD cancellation (LAC) function has been assigned to an intelligent input terminal and the LAC
terminal is turned on, the selected acceleration and deceleration patterns are ignored, and the output
frequency is quickly adjusted to that specified by the frequency command.
(3) Curvature of EL-S-curve pattern
When using the EL-S-curve pattern, you can set the curvatures (A150 to A153) individually for
acceleration and deceleration.
If all curvatures are set to 50%, the EL-S-curve pattern will be equivalent to the S-curve pattern.
4.2.26 Energy-saver operation
The energy-saver operation function allows you to automatically minimize
the inverter output power while the inverter is driving the motor at
constant speed. This function is suited to operating a fan, pump, or other
load that has a reduced-torque characteristic.
To use this function, specify "01" for the operation mode selection (A085).
Use the energy saving mode tuning function (A086) to adjust the response and accuracy of the
energy-saver operation.
The energy-saver operation function controls the inverter operation comparatively slowly. Therefore, if a
sudden change in the load occurs (e.g., impact load is applied), the motor may stall, and, consequently,
the inverter may trip because of overcurrent.
Item Function
code
Data
Description
00 Normal
operation
01 Energy-saving
operation
Operation mode selection
A085
02 Fuzzy
operation
Item Function
code
Data
Response
Accuracy
Energy saving mode tuning
A086
0
100
Slow
Quick
High
Low
96.9
82.4
17.6
3.1
25 50
75
10
02
10 02
99.6
93.8
35
25
50
75
10
10
02
87.5
68.4
64.6
65
35.4
0.39
25
50
75
10
02
31.6
12.5
6.25
Output frequency (Hz)
Output frequency (Hz)
Output frequency (Hz)
Target
frequency
(100%)
Target
frequency
(100%)
Target
frequency
(100%)
Acceleration time (100%) to reach
the set output frequency
Acceleration time (100%) to reach
the set output frequency
Acceleration time (100%) to reach
the set output frequency
Time Time Time
A085: Operation mode selection
A086: Energy saving mode tuning
Related code
100
50
Time (s)
Output frequency rate (%)
Curvature for
acceleration 2
(A151)
Curvature for
deceleration 1
(A152)
Curvature for
deceleration 2
(A153)
Curvature for
acceleration 1 (A150)
Summary of Contents for SJ700B SERIES
Page 15: ...Contents xiii Index Index Index 1 ...
Page 17: ......
Page 22: ......
Page 45: ......
Page 59: ......
Page 223: ......
Page 237: ......
Page 245: ......
Page 251: ...Chapter 7 Specifications 7 6 SJ700B 450 to 550HFF 5 Cable hole φ41 ...
Page 253: ......