Chapter 4 Explanation of Functions
4 - 123
(vii) 06 command: This command reads a specified setting item from the inverter.
- Transmission frame
Frame format
STX Station
No.
Command
Parameter
BCC
CR
Description
Data
size Setting
STX
Control code (Start of TeXt)
1 byte
STX (0x02)
Station No.
Station number of control-target
inverter
2 bytes
01 to 32
Command Command to be transmitted
2 bytes
06
Parameter Data parameter number
4 bytes
See Note 12.
BCC
Block check code
2 bytes
XOR of the items from "Station No." to "Data."
See Item (3) of this section.
CR
Control code (Carriage Return)
1 byte
CR (0x0D)
Note 12: The parameters that can be specified for reading are F002 to F004, A001 to A153, b001 to b132,
C001 to C159, H003 to H073, and P001 to P131. (To read the F001 parameter, use the 01
command.)
- Response frame
Positive response:
Frame format
STX Station
No. ACK
Data
BCC
CR
Description
Data
size Setting
STX
Control code (Start of TeXt)
1 byte
STX (0x02)
Station No.
Station number of control-target
inverter
2 bytes
01 to 32
ACK
Control code (acknowledgement)
1 byte
ACK (0x06)
Data
Data to be sent (decimal ASCII
code)
8 bytes
See Note 13.
BCC
Block check code
2 bytes
XOR of the items from "Station No." to "Data."
See Item (3) of this section.
CR
Control code (Carriage Return)
1 byte
CR (0x0D)
Note 13: When the read parameter is an selection item, the Data part contains the code data
corresponding to the selection.
The code data corresponding to "H003" or "H203" (motor capacity selection) is as follows:
Code
data
00 01 02 03 04 05 06 07 08 09 10
Japan or U.S.A. mode
(b085 = 00 or 02)
0.2 kW
-
0.4
-
0.75
-
1.5
2.2
-
3.7
-
EU mode (b085 = 01)
0.2 kW 0.37
-
0.55
0.75
1.1
1.5
2.2 3.0
-
4.0
Code
data
11 12 13 14 15 16 17 18 19 20 21
Japan or U.S.A. mode
(b085 = 00 or 02)
5.5
kW
7.5
11 15 18.5
22 30 37 45 55 75
EU mode (b085 = 01)
5.5 kW
7.5
11
15
18.5
22
30
37
45
55
75
Code
data
22
23
24
25
26
Japan or U.S.A. mode
(b085 = 00 or 02)
90kW
110
132
150
160
EU mode (b085 = 01)
90kW
110
132
150
160
For the value contained in the Data part when the read parameter is a numerical item, see the list of
function codes.
(Example) When the setting of the acceleration (1) time (F002) is 30.00 seconds, the Data part contains
"3000".
Negative response: See Item (2)-(ii) of this section.