Chapter 4 Explanation of Functions
4 - 46
4.2.39 Intelligent input terminal setting
You can assign the functions described below to intelligent input
terminals [1] to [8]. To assign the desired functions to the
terminals, specify the desired data listed in the table below for
terminal settings "C001" to "C008". For example, "C001"
corresponds to intelligent input terminal [1].
You can select the a-contact or b-contact input for individual intelligent input terminals.
You can assign one function only to an intelligent input terminal. If you have attempted to assign a function
to two or more intelligent input terminals, the function is assigned to only the terminal to which you have
last attempted assignment. Function data "NO" (no assign) is assigned to other terminals, and those
terminals are ineffective in terms of functions.
After assigning the desired functions to intelligent input terminals [1] to [8], confirm that the assigned
functions have been stored on the inverter.
Function code
Data
Description
Reference item
Page
01
RV: Reverse RUN command
Operation command
-
02
CF1: Multispeed 1 setting (binary operation)
03
CF2: Multispeed 2 setting (binary operation)
04
CF3: Multispeed 3 setting (binary operation)
05
CF4: Multispeed 4 setting (binary operation)
Multispeed operation function
4-48
06
JG: Jogging
Jogging operation function
4-50
07
DB: External DC braking
DC braking (external DC braking) function
4-20
08
SET: Set 2nd motor data
2nd/3rd motor control function
4-50
09
2CH: 2-stage acceleration/deceleration
2-stage acceleration/deceleration function
4-30
11
FRS: Free-run stop
Free-run stop function
4-53
12
EXT: External trip
External trip function
4-58
13
USP: Unattended start protection
Unattended start protection function
4-57
14
CS: Commercial power source enable
Commercial power supply switching function
4-54
15
SFT: Software lock (control circuit terminal block) Software lock function
4-52
16
AT: Analog input voltage/current select
External analog input setting function
4-12
17
SET3: 3rd motor control
2nd/3rd motor control function
4-51
18 RS:
Reset
Reset
4-55
20
STA: Starting by 3-wire input
21
STP: Stopping by 3-wire input
22
F/R: Forward/reverse switching by 3-wire input
3-wire input function
4-58
23
PID: PID disable
24
PIDC: PID reset
PID function
4-26
26
CAS: Control gain setting
Control gain switching function
4-59
27
UP: Remote control UP function
28
DWN: Remote control DOWN function
29
DWN: Remote control data clearing
Remote control (UP/DWN) function
4-57
31
OPE: Forcible operation
Forcible-operation function
4-52
32
SF1: Multispeed 1 setting (bit operation)
33
SF2: Multispeed 2 setting (bit operation)
34
SF3: Multispeed 3 setting (bit operation)
35
SF4: Multispeed 4 setting (bit operation)
36
SF5: Multispeed 5 setting (bit operation)
37
SF6: Multispeed 6 setting (bit operation)
38
SF7: Multispeed 7 setting (bit operation)
Multispeed operation function
4-48
39
OLR: Overload restriction selection
Overload restriction function
4-40
40
TL: Torque limit enable
41
TRQ1: Torque limit selection bit 1
42
TRQ2: Torque limit selection bit 2
Torque limitation function
4-93
43
PPI: P/PI mode selection
P/PI switching function
4-59
44
BOK: Braking confirmation
Brake control function
4-82
45 ORT:
Orientation
Orientation
function
4-105
46
LAC: LAD cancellation
LAD cancellation function
4-10
47
PCLR: Clearance of position deviation
48
STAT: Pulse train position command input enable
V2 control mode selection function
4-97
C001 to C008
50
ADD: Trigger for frequency addition (A145)
Frequency addition function
4-14
C001 to C008: Terminal [1] to [8] functions
Related code
Summary of Contents for SJ700B SERIES
Page 15: ...Contents xiii Index Index Index 1 ...
Page 17: ......
Page 22: ......
Page 45: ......
Page 59: ......
Page 223: ......
Page 237: ......
Page 245: ......
Page 251: ...Chapter 7 Specifications 7 6 SJ700B 450 to 550HFF 5 Cable hole φ41 ...
Page 253: ......