Chapter 4 Explanation of Functions
4 - 56
4.2.50 Unattended start protection (USP) function
The unattended start protection function allows you to make the
inverter trip with error code "E13" displayed if the inverter power is
turned on when an operation command has been turned on.
You can recover the inverter from tripping by performing the reset operation or turning the operation
command off. (See example 1.)
If the inverter is recovered from tripping with the operation command left turned on, the inverter will start
operation immediately after recovery. (See example 2.)
The inverter can operate normally when an operation command is turned on after the inverter power is
turned on. (See example 3.)
To use this function, assign function "13" (USP) to one of the terminal [1] to [8] functions (C001 to C008).
The following charts show examples of the timing of the unattended start protection operation:
(Example 1)
(Example 2)
(Example 3)
Item Function
code
Data
Description
Terminal [1] to [8] functions
C001 to C008
13
USP: Unattended start protection
4.2.51 Remote control function (UP and DWN)
The remote control function allows you to change the inverter output
frequency by operating the UP and DWN terminals (intelligent input
terminals).
To use this function, assign functions "27" (UP) and "28" (DWN) to two of the terminal [1] to [8] functions
(C001 to C008).
- This function is only effective for multispeed operation when "01 (terminal)" or "02 (oprater)" has been
specified for the frequency source setting (A001). If "01" (control circuit terminal block) has been specified,
this function is only effective when the analog command holding function (AHD) is enabled. (see 4.2.56)
This function is ineffective when the external analog input has been specified for the frequency source
setting (A001). This function cannot be used to set frequencies for jogging operation.
When the UP or DWN terminal is on, the 1st, 2nd, and 3rd acceleration/deceleration time follows the
settings of "F002", "F003/F202", "F203/F302", and "F303". To switch between the 1st, 2nd, and 3rd
controls, assign function "08" (SET) and "17" (SET3) to intelligent input terminals, and turn on and off the
SET and SET3 terminals for switching.
You can store the frequency settings adjusted using the remote control function (UP and DWN signals).
Set 01 (enable) on C101 to store the frequency settings.
You can also clear the stored frequency settings. Assign function "29" (UDC) to an intelligent input terminal,
and turn on or off the UDC terminal to clear or store, respectively, the frequency settings adjusted with the
UP and DWN signals. In this case 0Hz is set as initial value.
Item Function
code
Data
Description
27
UP: Remote control UP function
28
DWN: Remote control DOWN function
Terminal function
C001 to C008
29
DWN: Remote control data clearing
00
Disabling the storage of frequency settings
Up/Down memory mode
selection
C101
01
Enabling the storage of frequency settings (*1)
*1 Do not operate the UP or DWN terminal after the inverter power is shut off. Otherwise, the frequency
settings may not be stored correctly.
C001 to C008: Terminal [1] to [8] functions
Related code
Power
supply
FW
USP
RS
Alarm
Output
frequency
C101: Up/Down memory mode selection
C001 to C008: Terminal [1] to [8] functions
Related code
Power
supply
FW
USP
RS
Alarm
Output
frequency
Power
supply
FW
USP
RS
Alarm
Output
frequency
Operation command
(FW or RV)
Turning on the UP and DWN terminals
at the same time disables acceleration
and deceleration.
Output
frequency
UP
DWN
Summary of Contents for SJ700B SERIES
Page 15: ...Contents xiii Index Index Index 1 ...
Page 17: ......
Page 22: ......
Page 45: ......
Page 59: ......
Page 223: ......
Page 237: ......
Page 245: ......
Page 251: ...Chapter 7 Specifications 7 6 SJ700B 450 to 550HFF 5 Cable hole φ41 ...
Page 253: ......