Chapter 8 List of Data Settings
8 - 8
Code
Function name
Monitored data or setting
Default
Setting during
operation
(allowed or not)
Change during
operation
(allowed or not)
Page
b078
Cumulative input power data
clearance
Clearance by setting "01" and pressing the STR key
00
{
{
b079
Cumulative input power display gain
setting
1. to 1000.
1.
{
{
4-4
b082
Start frequency adjustment
0.10 to 9.99 (Hz)
0.50
¯
{
4-42
b083
Carrier frequency setting
0.5 to 12.0 (kHz) (subject to derating)
3.0
¯
¯
4-43
b084
Initialization mode (parameters or
trip history)
00 (clearing the trip history), 01 (initializing the data),
02 (clearing the trip history and initializing the data)
00
¯
¯
b085
Country code for initialization
00 (Japan), 01 (EU), 02 (U.S.A.)
01
¯
¯
4-75
b086
Frequency scaling conversion factor
0.1 to 99.0
1.0
{
{
4-2
b087
STOP key enable
00 (enabling), 01 (disabling), 02 (disabling only the function to stop)
00
¯
{
4-9
b088
Restart mode after FRS
00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (starting with
active matching frequency)
00
¯
{
4-52
b089
Automatic carrier frequency
reduction
00: invalid, 01: valid
00
¯
¯
4-44
b090
Dynamic braking usage ratio
0.0 to 100.0 (%)
0.0
¯
{
4-45
b091
Stop mode selection
00 (deceleration until stop), 01 (free-run stop)
00
¯
{
4-9
b092 Cooling
fan
control
00 (always operating the fan), 01 (operating the fan only during inverter
operation [including 5 minutes after power-on and power-off])
00
¯
{
b095
Dynamic braking control
00 (disabling), 01 (enabling [disabling while the motor is topped]), 02 (enabling
[enabling also while the motor is topped])
00
¯
{
b096
Dynamic braking activation level
330 to 380, 660 to 760(V)
360/
720
¯
{
4-45
b098
Thermistor for thermal protection
control
00 (disabling the thermistor), 01 (enabling the thermistor with PTC), 02
(enabling the thermistor with NTC)
00
¯
{
Oth
e
rs
b099
Thermal protection level setting
0. to 9999. (
Ω
)
3000.
¯
{
4-72
b100
Free-setting V/f frequency (1)
0. to "free-setting V/f frequency (2)" (Hz)
0.
¯
¯
b101
Free-setting V/f voltage (1)
0.0 to 800.0 (V)
0.0
¯
¯
b102
Free-setting V/f frequency (2)
0. to "free-setting V/f frequency (3)" (Hz)
0.
¯
¯
b103
Free-setting V/f voltage (2)
0.0 to 800.0 (V)
0.0
¯
¯
b104
Free-setting V/f frequency (3)
0. to "free-setting V/f frequency (4)" (Hz)
0.
¯
¯
b105
Free-setting V/f voltage (3)
0.0 to 800.0 (V)
0.0
¯
¯
b106
Free-setting V/f frequency (4)
0. to "free-setting V/f frequency (5)" (Hz)
0.
¯
¯
b107
Free-setting V/f voltage (4)
0.0 to 800.0 (V)
0.0
¯
¯
b108
Free-setting V/f frequency (5)
0. to "free-setting V/f frequency (6)" (Hz)
0.
¯
¯
b109
Free-setting V/f voltage (5)
0.0 to 800.0 (V)
0.0
¯
¯
b110
Free-setting V/f frequency (6)
0. to "free-setting V/f frequency (7)" (Hz)
0.
¯
¯
b111
Free-setting V/f voltage (6)
0.0 to 800.0 (V)
0.0
¯
¯
b112
Free-setting V/f frequency (7)
0. to 400. (Hz)
0.
¯
¯
F
re
e
se
tti
n
g
o
f V
/f ch
a
ra
c
te
ri
s
ti
c
b113
Free-setting V/f voltage (7)
0.0 to 800.0 (V)
0.0
¯
¯
4-17
b120
Brake Control Enable
00 (disabling), 01 (enabling)
00
¯
{
b121
Brake Wait Time for Release
0.00 to 5.00 (s)
0.00
¯
{
b122
Brake Wait Time for Acceleration
0.00 to 5.00 (s)
0.00
¯
{
b123
Brake Wait Time for Stopping
0.00 to 5.00 (s)
0.00
¯
{
b124
Brake Wait Time for Confirmation
0.00 to 5.00 (s)
0.00
¯
{
b125
Brake Release Frequency Setting
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
{
b126
Brake Release Current Setting
0.0 to 1.50 x "rated current"
Rated
current of
inverter
¯
{
b127
Braking frequency
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
{
4-81
b130
Overvoltage suppression enable
00 (disabling the restraint), 01 (controlled deceleration), 02 (enabling
acceleration)
00
¯
{
b131
Overvoltage suppression level
660 to 780 (V) (400 V class model)
380/
760
¯
{
b132
Acceleration and deceleration rate at
overvoltage suppression
0.10 to 30.00 (s)
1.00
¯
{
b133
Overvoltage suppression propotional
gain
0.00 to 2.55
0.50
{
{
Oth
e
rs
b134
Overvoltage suppression Integral
time
0.000 to 9.999 / 10.00 to 65.53 (s)
0.060
{
{
4-41