APPENDIX PARAMETER OBJECT LISTS
40
Function
Inst
Attr
Size
Monitoring/Setting Range
Magnifi-
cation
Access
rule
Com
mand
Selection of retry after tripping
(Param409)
1
108
1
00(Tripping)/01(Starting with 0 Hz)/
02(Starting with matching
frequency)/
03(Tripping after deceleration and
stopping with matching frequency)/
04(Restarting with active matching
frequency)
1
Get/Set
b008
Selection of retry count after
over-voltage (Param410)
1
109
1
00(16 times)/01(Unlimited)
1
Get/Set
b009
Selection of retry count after
over-voltage or over current
(Param411)
1
110
1
1 to 3(times)
1
Get/Set
b010
Retry wait time after tripping
(Param412)
1
111
2
0.3 to 100.0(s)
10
Get/Set
b011
E-Thermal Level (Param150)
1
112
2
20 to 100(%)(constant current 1%)
1
Get/Set
b012
2nd E-ThermalLvl (Param342)
2
112
2
20 to 100(%)(constant current 1%)
1
Get/Set
b212
3rd E-ThermalLvl (Param373)
3
112
2
20 to 100(%)(constant current 1%)
1
Get/Set
b312
E-ThermalCharSel (Param151)
1
113
1
00(Reduced torque)/
01(Constant torque)/
02(Free setting)
1
Get/Set
b013
2ndEThermCharSel (Param343)
2
113
1
00(Reduced torque)/
01(Constant torque)/
02(Free setting)
1
Get/Set
b213
3rdEThermCharSel (Param374)
3
113
1
00(Reduced torque)/
01(Constant torque)/
02(Free setting)
1
Get/Set
b313
E-Thermal Freq 1 (Param152)
1
115
2
0 to 400(Hz)
1
Get/Set
b015
E-Thermal Cur 1 (Param153)
1
116
2
0.0 to 999.9(A)
10
Get/Set
b016
E-Thermal Freq 2 (Param154)
1
117
2
0 to 400(Hz)
1
Get/Set
b017
E-Thermal Cur 2 (Param155)
1
118
2
0.0 to 999.9(A)
10
Get/Set
b018
E-Thermal Freq 3 (Param156)
1
119
2
0 to 400(Hz)
1
Get/Set
b019
E-Thermal Cur 3 (Param157)
1
120
2
0.0 to 999.9(A)
10
Get/Set
b020
OL Limit Enable (Param158)
1
121
1
00(Inactive)/01(Inactive at dec 1)/
02(Active at const 1)/
03(Inactive at dec 2)
1
Get/Set
b021
OL Limit Level (Param159)
1
122
2
20 to 200(%) (~55KW)
20 to 180(%) (75~132KW)
(constant current 1%)
1
Get/Set
b022
OL Limit Const (Param160)
1
123
2
0.10 to 30.00
100
Get/Set
b023
OL Limit Enable2 (Param161)
1
124
1
00(Inactive)/01(Inactive at dec 1)/
02(Active at const 1)/
03(Inactive at dec 2)
1
Get/Set
b024
OL Limit Level 2 (Param162)
1
125
2
20 to 200(%) (~55KW)
20 to 180(%) (75~132KW)
(constant current 1%)
1
Get/Set
b025
OL Limit Const 2 (Param163)
1
126
2
0.1 to 30.00
100
Get/Set
b026
Over-current suppression enable
(Param413)
1
127
1
00(Invalid)/01(Valid)
1
Get/Set
b027
Active frequency matching, scan
start frequency (Param414)
1
128
2
20.0 to 200.0(%) (~55KW)
20.0 to 180.0(%) (75~132KW)
10
Get/Set
b028
Active frequency matching,
scan-time constant (Param415)
1
129
2
0.10 to 30.00(s)
100
Get/Set
b029
Active frequency matching,
restart frequency select
(Param416)
1
130
1
00(Frequency at the last shutoff)/
01(Maximum Frequency)/
02(Set Frequency)
1
Get/Set
b030
SoftLock ModeSel (Param376)
1
131
1
00(SFT - All param)/
01(SFT - Only freq)/
02(All param)/03(Only freq)/
10(Change mode on run)
1
Get/Set
b031
Run/P-ONTime Lvl (Param164)
1
134
2
0 to 65535(hr)
1
Get/Set
b034
FW/RV Restrict (Param165)
1
135
1
00(FW/RV Enable)/
01(Forward only)/02(Reverse only)
1
Get/Set
b035
ReducedV TimeSel (Param166)
1
136
1
00 to 255
1
Get/Set
b036