CHAPTER6 DEVICENET COMMUNICATION FUNCTION
14
SJ-DN2 to Master: Instance71 (P047: 71)
Byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
0
At
Reference
Ref From
Net
Ctrl From
Net
Ready
Running2
(Rev)
Running1
(Fwd)
Warning
Faulted
1
Drive Status
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
Data
Contents
Faulted
It indicates the inverter is in a fault detecting state.
0:Normal 1:During detecting fault state
Warning
It indicates the inverter is in a warning detecting state.
0:Normal
1:During detecting warning (When there is contradiction on the inverter
setting.).
Running1(Fwd)
It indicates inverter’s running condition.
0:Stop / During reverse run 1:During forward run
Running2(Rev)
It indicates inverter’s running condition.
0:Stop / During forward run 1:During reverse run
Ready
It indicates the inverter ready for drive.
0:Except Drive status: 3,4,5.
1:Complete ready to drive (Drive Status: 3,4,5).
Ctrl From Net
It indicates selection state for inputting the inverter operational command
0:Operation command selection(A002) is valid to set.
1:Operation command from DeviceNet is valid.
Ref From Net
It indicates selection state for inputting the inverter frequency command.
0:Frequency command selection(A001) is valid to set.
1:Frequency command from DeviceNet is valid.
At Reference
It indicates arrival frequency detecting state for the inverter.
0:During stop / During accelerate or decelerate
1:Arrival frequency
Drive Status
It indicates inverter status.
1:Startup (Only R
0
-T
0
power supply is ON)
2:Not Ready (Just after turn on power supply)
3:Ready (Able to activate the inverter)
4:Enabled (Inverter is running by run command)
5:Stopping (Inverter is decelerating by stop command)
6:Fault Stop (Inverter is decelerating because trip is detected)
7:Faulted (Trip condition)
Speed Actual
It shows inverter speed.
[P49:Except for 0]
Rotational speed monitor: Speed Actual(min
-1
) / 2
SS
SS: Speed scale
Range of monitor:0-24000(min
-1
) (Resolution: 1min
-1
) Magnification: 1 time
e.g.) When Speed Actual is 03E8(Hex) (Speed scale:0)
Speed Actual=03E8(Hex)/2
0
=1000/2
0
=1000(min
-1
)
[P049:0]
Current frequency display (Resolution: 0.01Hz).
Range of monitor:0.00 to 400.00(Hz) Magnification: 100 time