CHAPTER7 COUNTERMEASURE FOR ABNORMALITY
23
7.5 Other notes
When SJ-DN2 is installed and the Inverter’s setting is below, the behavior of the inverter will be as following
by MFG No.
Operating mode select (A002) setting: 02(REM)
(1) before MFG NO. : XXEGXXXXXXXXXXXX
The Inverter will be automatically reset from fault status when it occurs trip while driving from DeviceNet
command. Case of the inverter drives again, please reset run command again after release run command.
(2) MFG No. : XXEGXXXXXXXXXXXX and after
The Inverter will be trip status. Case of the inverter drives again, please reset the run command again after
removing trip cause.