APPENDIX PARAMETER OBJECT LISTS
25
Function
Inst
Attr
Size
Monitoring/Setting Range
Magnifi-
cation
Access
rule
Com-
mand
Trip 4 RUN time (Param40)
1
144
4
0 to 999999(hr)
1
Get
d084
Trip 4 P-ON time (Param41)
1
145
4
0 to 999999(hr)
1
Get
d084
Trip 5 Cause (Param42)
1
146
4
E01.X to E79.X (E??:Trip cause,
X:running condition)
See 6.3.3 Hitachi inverter I/O
Instance(Instance 101)
1
Get
d085
Trip 5 frequency (Param43)
1
147
4
0.00 to 400.00(Hz)
100
Get
d085
Trip 5 Current (Param44)
1
148
2
0.0 to 999.9(A)
10
Get
d085
Trip 5 DC Voltage (Param45)
1
149
2
0.0 to 600.0(V)
10
Get
d085
Trip 5 RUN time (Param46)
1
150
4
0 to 999999(hr)
1
Get
d085
Trip 5 P-ON time (Param47)
1
151
4
0 to 999999(hr)
1
Get
d085
Trip 6 Cause (Param48)
1
152
4
E01.X to E79.X (E??:Trip cause,
X:running condition)
See 6.3.3 Hitachi inverter I/O
Instance(Instance 101)
1
Get
d086
Trip 6 frequency (Param49)
1
153
4
0.00 to 400.00(Hz)
100
Get
d086
Trip 6 Current (Param50)
1
154
2
0.0 to 999.9(A)
10
Get
d086
Trip 6 DC Voltage (Param51)
1
155
2
0.0 to 600.0(V)
10
Get
d086
Trip 6 RUN time (Param52)
1
156
4
0 to 999999(hr)
1
Get
d086
Trip 6 P-ON time 6(Param53)
1
157
4
0 to 999999(hr)
1
Get
d086
Warning Monitor (Param54)
1
158
1
00 (No Warning)
01(W001) 02(W002) 03(W004)
04(W005) 05(W006) 06(W009)
07(W201) 08(W202) 09(W204)
10(W205) 11(W206) 12(W209)
13(W304) 14(W305) 15(W306)
16(W309) 17(W012) 18(W015)
19(W016) 21(W212)
22(W215) 23(W216) 24(W219)
25(W021) 26(W025) 27(W026)
28(W029) 29(W221) 30(W225)
31(W226) 32(W229) 33(W031)
34(W231) 35(W032) 36(W232)
37(W035) 38(W235) 39(W335)
40(W036) 41(W037) 42(W085)
43(W285) 44(W385) 45(W086)
46(W091) 47(W291) 48(W092)
49(W292) 50(W095) 51(W295)
52(W395) 53(W096) 54(W110)
55(W120)
1
Get
d090
Frequency Setting (Param60)
1
159
4
0.00 to 400.00(Hz)
100
Get/Set
F001
Accel Time 1 (Param61)
1
160
4
0.01 to 3600.00(s)
100
Get/Set
F002
2nd Accel Time 1 (Param337)
2
160
4
0.01 to 3600.00(s)
100
Get/Set
F202
3rd Accel Time 1 (Param372)
3
160
4
0.01 to 3600.00(s)
100
Get/Set
F302
Decel Time 1(Param62)
1
161
4
0.01 to 3600.00(s)
100
Get/Set
F003
2nd Decel Time 1(Param338)
2
161
4
0.01 to 3600.00(s)
100
Get/Set
F203
3rd Decel Time 1 (Param373)
3
161
4
0.01 to 3600.00(s)
100
Get/Set
F303
Direction Setting (Param63)
1
162
1
00(Forward)/01(Reverse)
1
Get/Set
F004
Support service
Service name
Code
Get_Attribute_Single
H’0E
Set_Attribute_Single
H’10
(2) Extend Group A object Class ID=101
Function
Inst
Attr
Size
Monitoring/Setting Range
Magnifi-
cation
Access
rule
Com-
mand
Freq-Setting Sel (Param64)
1
101
1
00(Volume)/01(Terminal)/
02(Operator)/03(RS485)/
04(Option1)/05(Option2)
1
Get/Set
A001
Operating Mode Sel (Param65)
1
102
1
01(Terminal)/02(Operator)/
03(RS485)/04(Option1)/
05(Option2)
1
Get/Set
A002
Base Frequency (Param56)
1
103
2
30 to 400(Hz)
1
Get/Set
A003
2nd Base Frequency (Param334)
2
103
2
30 to 400(Hz)
1
Get/Set
A203
3rd Base Frequency (Param371)
3
103
2
30 to 400(Hz)
1
Get/Set
A303
Max Frequency (Param55)
1
104
2
30 to 400(Hz)
1
Get/Set
A004
2ndMaxFrequency (Param333)
2
104
2
30 to 400(Hz)
1
Get/Set
A204
3rd Max Frequency (Param370)
3
104
2
30 to 400(Hz)
1
Get/Set
A304
AT Function Sel (Param66)
1
105
1
00(O/OI)/01(O/O2)
1
Get/Set
A005