APPENDIX PARAMETER OBJECT LISTS
45
Function
Inst
Attr
Size
Monitoring/Setting Range
Magnifi-
cation
Access
rule
Com
mand
OV-TRQ FW-R (Param256)
1
158
1
0 to 200(%) (~55KW)
0 to 180(%) (75~132KW)
(constant current 1%)
1
Get/Set
C058
Thermal Warn Lvl (Param257)
1
161
2
0 to 100(%)
1
Get/Set
C061
AlarmMode Select (Param258)
1
162
1
00(Invalid)/01(3bit)/02(4bit)
1
Get/Set
C062
ZERO Speed Level (Param259)
1
163
2
0.00 to 100.00(Hz)
100
Get/Set
C063
CommSpeed Select (Param260)
1
171
1
02(loop back)/
03(2400bps)/04(4800bps)/
05(9600bps)/06(19200bps)
1
Get/Set
C071
Comm ID Select (Param261)
1
172
1
1 to 32
1
Get/Set
C072
CommBitLengthSel (Param262)
1
173
1
7(7bit)/8(8bit)
1
Get/Set
C073
CommParitySelect (Param263)
1
174
1
00(No Parity)/01(Even Parity)/
02(Odd Parity)
1
Get/Set
C074
Comm StopBit Sel (Param264)
1
175
1
1(1bit)/2(2bit)
1
Get/Set
C075
Communication timeout limit
before tripping (Param443)
1
177
2
0.00 to 99.99(s)
100
Get/Set
C077
Comm Wait Time (Param265)
1
178
2
0 to 1000(ms)
1
Get/Set
C078
Communication mode selection
(Param444)
1
179
1
00(ASCII)/01(Modbus-RTU)
1
Get/Set
C079
O Adjustment (Param266)
1
181
2
0 to 65535
1
Get/Set
C081
OI Adjustment (Param267)
1
182
2
0 to 65535
1
Get/Set
C082
O2 Adjustment (Param268)
1
183
2
0 to 65535
1
Get/Set
C083
Therm-Adjustment (Param269)
1
185
2
0.0 to 1000.0
10
Get/Set
C085
Support service
Service name
Code
Get_Attribute_Single
H’0E
Set_Attribute_Single
H’10
(6) Extend Group C object Class ID=106
Function
Inst
Attr
Size
Monitoring/Setting Range
Magnifi-
cation
Access
rule
Com-
mand
UP/DWN Selection (Param270)
1
101
1
00(Not keep)/01(Keep)
1
Get/Set
C101
Reset Selection (Param271)
1
102
1
00(Reset at close)/
01(Reset at open)/
02(Only trip clear)/03(Only Trip
Reset)
1
Get/Set
C102
Reset f MacthSel (Param272)
1
103
1
00(0Hz start)/
01(Synchronize)/02(Restarting with
Active Matching Frequency)
1
Get/Set
C103
FM gain adjustment (Param446)
1
105
2
50 to 200(%)
1
Get/Set
C105
AM gain adjustment (Param447)
1
106
2
50 to 200(%)
1
Get/Set
C106
AMI gain adjustment (Param448)
1
107
2
50 to 200(%)
1
Get/Set
C107
AM bias adjustment (Param449)
1
109
1
0 to 100(%)
1
Get/Set
C109
AMI bias adjustment (Param450)
1
110
1
0 to 100(%)
1
Get/Set
C110
OL Alarm Level 2 (Param273)
1
111
2
0 to 200(%) (~55KW)
0 to 180(%) (75~132KW)
(constant current 1%)
1
Get/Set
C111
O Zero Adjustment (Param274)
1
121
2
0 to 65535
1
Get/Set
C121
OI Zero Adjustment (Param275)
1
122
2
0 to 65535
1
Get/Set
C122
O2 Zero Adjustment (Param276)
1
123
2
0 to 65535
1
Get/Set
C123
Output 11 on-delay time
(Param451)
1
130
2
0.0 to 100.0(s)
10
Get/Set
C130
Output 11 off-delay time
(Param452)
1
131
2
0.0 to 100.0(s)
10
Get/Set
C131
Output 12 on-delay time
(Param453)
1
132
2
0.0 to 100.0(s)
10
Get/Set
C132
Output 12 off-delay time
(Param454)
1
133
2
0.0 to 100.0(s)
10
Get/Set
C133
Output 13 on-delay time
(Param455)
1
134
2
0.0 to 100.0(s)
10
Get/Set
C134
Output 13 off-delay time
(Param456)
1
135
2
0.0 to 100.0(s)
10
Get/Set
C135