APPENDIX PARAMETER OBJECT LISTS
34
SJ700 Parameter Object List
(1) Inverter Data monitor/Basic Data Setting object. Class ID=100
Function
Inst
Attr
Size
Monitoring/Setting Range
Magnifi-
cation
Access
rule
Com-
mand
Inverter Mode (Param16)
1
100
1
00(SJ700)
1
Get
-
Rated Power (Param14)
1
101
1
00(0.20)/01(0.40)/02(0.75)/
03(1.50)/04(2.20)/05(3.70)/
06(5.50)/07(7.50)/08(11.0)/
09(15.0)/10(18.5)/11(22.0)/
12(30.0)/13(37.0)/14(45.0)/
15(55.0)/16(75.0)/17(90.0)/
18(110.0)/19(132.0)
1
Get
-
Rated Voltage (Param15)
1
102
1
00(200V)/01(400V)
1
Get
-
Output Frequency (Param1)
1
104
4
0.00 to 400.00(Hz)
100
Get
d001
Output Current (Param2)
1
105
2
0.0 to 6553.5(A)
10
Get
d002
Direction (Param3)
1
106
1
01(Forward)/00(Stopped)/
02(Reverse)
1
Get
d003
PID Feedback (Param4)
1
107
4
0.00 to 9999.00
100
Get
d004
Dig In Status (Param5)
1
108
2
Bit8 : Forward Bit7 : Dig input 8
Bit6 : Dig input 7 Bit5 : Dig input 6
Bit4 : Dig input 5 Bit3 : Dig input 4
Bit2 : Dig input 3 Bit1 : Dig input 2
Bit0 : Dig input 1
Close: 1, Open : 0
1
Get
d005
Dig Out Status (Param6)
1
109
2
Bit5 : Alarm
Bit4 : Dig output 15
Bit3 : Dig output 14
Bit2 : Dig output 13
Bit1 : Dig output 12
Bit0 : Dig output 11
Close: 1, Open : 0
1
Get
d006
Freq-conversion (Param7)
1
110
4
0.00 to 3996.00
100
Get
d007
Actual-frequency
monitoring(Param377)
1
163
4
-400.00 to 400.00(Hz)
100
Get
d008
Torque command monitoring
(Param378)
1
164
2
0 to 200(%)
1
Get
d009
Torque bias monitoring
(Param379)
1
165
2
-200 to +200(%)
1
Get
d010
Torque (Param8)
1
111
2
-200 to +200(%)
1
Get
d012
Output Voltage (Param9)
1
112
2
0.0 to 600.0(V)
10
Get
d013
Input Elect-Pow (Param10)
1
113
2
0.0 to 999.9(kW)
10
Get
d014
Cumulative power monitoring
(Param380)
1
114
4
0.00 to 999999.90
100
Get
d015
Elapsed Run time (Param11)
1
115
4
0 to 999999(hr)
1
Get
d016
Power ON time (Param12)
1
116
4
0 to 999999(hr)
1
Get
d017
DC Voltage (Param13)
1
118
2
0.0 to 999.9(V)
10
Get
d102
Heat sink temperature
monitoring (Param381)
1
117
2
-20.0 to 200.0(
℃
)
100
Get
d018
Motor temperature monitoring
(Param382)
1
119
2
-20.0 to 200.0(
℃
)
100
Get
d019
Life-check monitoring
(Param383)
1
166
1
Bit 1: Capacitor on main circuit
board
Bit 2: Cooling-fan speed drop
100
Get
d022
user monitor 0 (Param384)
1
169
4
-2147483647 to +2147483647
100
Get
d025
user monitor 1 (Param385)
1
170
4
-2147483647 to +2147483647
100
Get
d026
user monitor 2 (Param386)
1
171
4
-2147483647 to +2147483647
100
Get
d027
Pulse counter monitor
(Param387)
1
172
4
0 to 2147483647
100
Get
d028
Position command monitor
(Param388)
1
173
4
-1073741823 to +1073741823 (pls)
100
Get
d029
Position feedback monitor
(Param389)
1
174
4
-1073741823 to +1073741823 (pls)
100
Get
d030
Trip Counter (Param17)
1
121
2
0 to 65535
1
Get
d080
Trip 1 Cause (Param18)
1
122
4
E01.X to E79.X (E??:Trip cause,
X:running condition)
See 6.3.3 Hitachi inverter I/O
Instance(Instance 101)
1
Get
d081