APPENDIX PARAMETER OBJECT LISTS
32
(7) Extend Group H object Class ID=107
Function
Inst
Attr
Size
Monitoring/Setting Range
Magnifi-
cation
Access
rule
Com
mand
AutotuningSelect (Param283)
1
101
1
00(Invalid)/01(Valid(not rotate))/
02(Valid(rotate))
1
Get/Set
H001
Motor Constant (Param284)
1
102
1
00(Standard Motor)/
01(Offline Auto)/02(Online Auto)
1
Get/Set
H002
2nd Motor Constant (Param351)
2
102
1
00(Standard Motor)/
01(Offline Auto)/02(Online Auto)
1
Get/Set
H202
Allowable Motor (Param285)
1
103
1
Available setting range for EC:
00(0.20)/01(0.37)/03(0.55)/
04(0.75)/05(1.10)/06(1.50)/
07(2.20)/08(3.00)/10(4.00)/
11(5.50)/12(7.50)/13(11.0)/
14(15.0)/15(18.5)/16(22.0)/
17(30.0)/18(37.0)/19(45.0)/
20(55.0)/21(75.0)/22(90.00)/
23(110.0)/24(132.0)/25(150.0)/
26(160.0)
Available setting range for USA:
00(0.20)/02(0.40)/04(0.75)/
06(1.50)/07(2.20)/09(3.70)/
11(5.50)/12(7.50)/13(11.0)/
14(15.0)/15(18.5)/16(22.0)/
17(30.0)/18(37.0)/19(45.0)/
20(55.0)/21(75.0)/22(90.00)/
23(110.0)/24(132.0)/25(150.0)/
26(160.0)
1
Get/Set
H003
2nd Allowable Motor (Param352)
2
103
1
Same above
1
Get/Set
H203
MotorPole Select (Param286)
1
104
1
0(2P)/1(4P)/2(6P)/3(8P)
1
Get/Set
H004
2nd MotorPole Select(Param353)
2
104
1
0(2P)/1(4P)/2(6P)/3(8P)
1
Get/Set
H204
Speed Response (Param287)
1
105
2
0.001 to 65.535
1000
Get/Set
H005
2nd Speed Response(Param354)
2
105
2
0.001 to 65.535
1000
Get/Set
H205
StabilizedFactor (Param288)
1
106
2
0 to 255
1
Get/Set
H006
2nd StabilizedFactor (Param355)
2
106
2
0 to 255
1
Get/Set
H206
3rd StabilizedFactor (Param382)
3
106
2
0 to 255
1
Get/Set
H306
Motor-Const R1 (Param289)
1
120
4
0.000 to 65.530( )
1000
Get/Set
H020
2nd Motor-Const R1 (Param356)
2
120
4
0.000 to 65.530( )
1000
Get/Set
H220
Motor-Const R2 (Param290)
1
121
4
0.000 to 65.530( )
1000
Get/Set
H021
2nd Motor-Const R2 (Param357)
2
121
4
0.000 to 65.530( ))
1000
Get/Set
H221
Motor-Const L (Param291)
1
122
4
0.00 to 655.30(mH)
100
Get/Set
H022
2nd Motor-Const L (Param358)
2
122
4
0.00 to 655.30(mH)
100
Get/Set
H222
Motor-Const I0 (Param292)
1
123
4
0.00 to 655.30(A)
100
Get/Set
H023
2nd Motor-Const I0 (Param359)
2
123
4
0.00 to 655.30(A)
100
Get/Set
H223
Motor-Const J (Param293)
1
124
4
0.001 to 9999(kgm
2
)
1000
Get/Set
H024
2nd Motor-Const J (Param360)
2
124
4
0.001 to 9999(kgm
2
)
1000
Get/Set
H224
Motor-Auto R1 (Param294)
1
130
4
0.000 to 65.530( )
1000
Get/Set
H030
2nd Motor-Auto R1 (Param361)
2
130
4
0.000 to 65.530( )
1000
Get/Set
H230
Motor-Auto R2 (Param295)
1
131
4
0.000 to 65.530( )
1000
Get/Set
H031
2nd Motor-Auto R2 (Param362)
2
131
4
0.000 to 65.530( )
1000
Get/Set
H231
Motor-Auto L (Param296)
1
132
4
0.00 to 655.30(mH)
100
Get/Set
H032
2nd Motor-Auto L (Param363)
2
132
4
0.00 to 655.30(mH)
100
Get/Set
H232
Motor-Auto I0 (Param297)
1
133
4
0.00 to 655.30(A)
100
Get/Set
H033
2nd Motor-Auto I0 (Param364)
2
133
4
0.00 to 655.30(A)
100
Get/Set
H233
Motor-Auto J (Param298)
1
134
4
0.001 to 9999(kgm
2
)
1000
Get/Set
H034
2nd Motor-Auto J (Param365)
2
134
4
0.001 to 9999(kgm
2
)
1000
Get/Set
H234
PIProportionGain (Param299)
1
150
2
0.0 to 1000(%)
10
Get/Set
H050
2nd PIProportionGain(Param366)
2
150
2
0.0 to 1000(%)
10
Get/Set
H250
PI Integrat-Gain (Param300)
1
151
2
0.0 to 1000(%)
10
Get/Set
H051
2nd PI Integrat-Gain (Param367)
2
151
2
0.0 to 1000(%)
10
Get/Set
H251
P ProportionGain (Param301)
1
152
2
0.01 to 10.00
100
Get/Set
H052
2nd P ProportionGain(Param368)
2
152
2
0.01 to 10.00
100
Get/Set
H252
0Hz-SLV Limit (Param302)
1
160
2
0.0 to 100(%)
10
Get/Set
H060
2nd 0Hz-SLV Limit (Param369)
2
160
2
0.0 to 100(%)
10
Get/Set
H260
PIProport-Gain2 (Param303)
1
170
2
0.0 to 1000(%)
10
Get/Set
H070
PIIntegrat-Gain2 (Param304)
1
171
2
0.0 to 1000(%)
10
Get/Set
H071
P Proport-Gain2 (Param305)
1
172
2
0.00 to 10.00
100
Get/Set
H072
Support service
Service name
Code
Get_Attribute_Single
H’0E
Set_Attribute_Single
H’10