Fault Detection
The AC drive has a comprehensive fault diagnostic system that includes several different
alarms and fault messages. Once a fault is detected, the corresponding protective functions
will be activated. The following faults are displayed as shown on the AC drive digital keypad
display.
Note
Not all faults can be cleared by resetting from the drive keypad. Some faults
can only be cleared by cycling power on the drive, and some faults cannot be
reset at all.
Code
Name
Possible Cause
Remedy
CrF1
Precharge
Charging relay control fault or
charging resistor damaged
Turn the drive off and then back
on again
Check the connections
Check the stability of the main
supply
Contact your local Schneider
Electric
representative
InFI
Unknown drive rating
The power card is different from the
card stored
Contact your local Schneider
Electric representative
InF2
Unknown or
incompatible power
board
The power card is incompatible with
the control card
Contact your local Schneider
Electric representative
InF3
Internal serial link
Communication interruption
between the internal cards
Contact your local Schneider
Electric representative
InF4
Invalid
industrialization zone
Inconsistent internal data
Contact your local Schneider
Electric representative
InF9
Current
measurement circuit
Current measurement is not
correct due to hardware circuit
Contact your local Schneider
Electric representative
----
Problem of
application Firmware
Invalid application firmware
update using the Multi-Loader tool
Flash again the application
firmware of the product
InFb
Internal thermal
sensor detected fault
The drive temperature sensor is
not operating correctly
The drive is in short circuit or
open
Contact your local Schneider
Electric representative
InFE
Internal CPU
Internal microprocessor
Turn the drive off and then back
on again
Contact your local Schneider
Electric representative
OCF
Overcurrent
Parameters in the Motor Control
menu (drC) are not set properly
Inertia or load too high
Mechanical locking
Check the parameters
Check the size of the
motor/drive/load
Check the state of the
mechanism
Connect line chokes
Reduce the Switching
Frequencies (SFr)
Check the ground connection of
drive, motor cable, and motor
insulation