Installation & Adjustments
Synergy 0.5 Turntable Stretch Wrapper Operation Manual
Highlight Industries, Inc. ● 2694 Prairie SW, Wyoming, Mi 49519 ● 1-800-531-2465
18
Programming Functions
All functions have been Highlight factory set and tested. The factory settings listed in this
manual are the drive manufacturer’s factory setting, not the Highlight Industries factory
settings. Refer to the Electrical Schematic Drive Parameters page of the Technical
References section for the Highlight factory settings. Some of the most commonly adjusted
programmable functions (parameters) are listed below.
Note
Refer to the drive manufacturers Operation Manual or website for complete lists
and explanations of the programming parameters.
I_O Menu
Code
Sub-
Code
Name/Description
Factory
Setting
tCC
Type of Control:
2C
– 2-wire control
3C
– 3-wire control
2C
AI1-
AI1t
Analog Input 1 Type:
5U
– 0-5VDC input voltage
10U
– 0-10VDC input voltage
0A
– 0-20mA current input
5U
r1
Relay Output 1 Assignment:
nO
– Not assigned
FLt
– No error detected
rUn
– Drive run
FLt
AO1-
AO1
Analog Output 1 Assignment:
nO
– Not Assigned
OCr
– Motor current
OFr
– Output Frequency
nO
AO1t
Analog Output 1 Type:
10U
– 0-10VDC
0A
– 0-20mA
4A
– 4-20mA
0A