Powering Hub and VSP with Different Voltage
Wire the Hub and VSP separately if using different voltages for both. If the new pump requires a dif-
ferent voltage than the old, run a separate source from the electrical panel. The Hub, which can be
powered by either 115 VAC or 230 VAC, can be powered by the existing timeclock or switch. Both
units need power constantly so if there is a switch or timeclock in the system, it must be set to run
continuously.
Powering Hub and Single Speed Pump with Same Voltage
Single speed pumps require the use of Smart Relay(s). High voltage connections are made directly
to Smart Relays which are turned on and off through a low voltage communication connection to the
OmniHub. Like the OmniHub, Smart Relays can be powered by either 115 VAC or 230 VAC.
Connect 115 VAC from the
panel, timeclock, outlet or
switch. Make sure Omni-
Hub is powered constantly.
Ground
115 VAC to Hub
Neutral
L1
230 VAC to VSP
Electrical Panel
Run separate
230 VAC con-
stant source to
13