The final reject load for the combined aural cabinets may be
calibrated by energizing aural PA cabinet “A” at 3 kW (or 6 kW for
20% aural power option) and adjust calibrate control R-103 on the
main controller for 2.5 volts at TP-7. The front panel display page
indicating the reject load powers should then read 1.5 kW (or 3 kW
for 20% aural option) on the appropriate aural meter page.
5.16
AGC Setup
The transmitter should be operating at normal ambient tempera-
ture and warmed up approximately 30 minutes. This procedure
is the same for visual and aural.
NOTE
The twelve turn potentiometers used for EXC ADJUST and SET
can be from different manufactures. Electrically they have the
same value but differ in the direction the control is rotated to
increase the voltage.
a. Reduce exciter power to zero, and switch AGC MODE
switch to OFF.
b. Increase exciter power for 100% transmitter power output.
c. Measure the exciter sample at the EXC test point. The
value should be between 1.2 and 1.5 volts DC.
d. Rotate the EXC ADJUST pot on top of AGC card to bring
the voltage within this range if needed.
e. Measure the transmitter sample at test point TX, and adjust SET
pot for the same or slightly less voltage that the exciter sample.
NOTE
It may be necessary to add or delete attenuation pad(s) in trans-
mitter sample line to obtain proper voltage.
f. Reduce transmitter power to zero.
g. Switch AGC MODE switch to ON.
h. Increase exciter power until transmitter power is 100%.
i. Adjust SET pot to reduce transmitter power to about 70%
for room temperatures near 70°F. If room temperature is
near 110°F adjust to 95%, and if near 50°F adjust for 65%.
j. Increase exciter drive to 100% power.
If there are problems with module overdrive faults when turning
ON the transmitter when the room is cold, adjust SET pot for less
power reduction.
If the transmitter sample voltage is much less than the exciter
sample, there may not be enough range for power reduction
adjustment.
NOTE
If adjusting the visual AGC changed the drive level, check adjust-
ment of the exciter precorrection for differential gain, ICPM, and
differential phase. Refer to the exciter manual.
5.17
Monitor Configuration Switches
Two eight-bit configuration switches on the monitor board are
used to configure the monitor system for use in a given transmit-
ter model. See Table 5-7 on page 5-11.
5.18
Lamp Test
The Main Controller board has a press-to-test switch to turn on
all Fault Status Indicator lamps.
5.19
AC Line Sample Calibration
The monitor board has three controls for calibration of the line
voltage readings. They are located just above and to the right of
the battery on the Monitor board.
WARNING
WHEN MEASURING THE LINE VOLTAGES, REMOVE ALL
POWER FROM THE CABINET, ATTACH THE TEST PROBES,
CLOSE THE CABINET, AND RE-ENERGIZE THE POWER TO
THE CABINET.
Measure line voltage at line sample kits. Adjust R-90 for phase
A-B to read the correct voltage on the display panel line infor-
mation screen.
Adjust R-91 for phase B-C, and R-92 for phase AC.
5.20
Slave Addressing
If the Slave Controller board is replaced or swapped for trou-
bleshooting purposes, the address must be set using S1. Ad-
dresses are shown in Table 5-6.
5.21
Slave Analog Channels Calibration
Disconnect the cable at J-6 on the slave controller. Measure the
voltage at pins 3 and 4, then reconnect the cable.
Call up the supply information page on the display panel, and
adjust R-46 to calibrate the PS-1 current reading to 100 amps per
1 volt measured.
Check that the other analog functions are being correctly dis-
played. The ratio of sample voltage to displayed supply voltage
value is 2.5 V with the cable removed = 50 V on the display.
J-6 functions
1-2 PS-1 volts
3-4 PS-1 current
5-6 PS-2 volts
7-8 PS-2 current
5.22
VSWR Protection Adjustments
5.22.1
Foldback
VSWR Foldback provides protection for the external RF system,
hybrids, diplexers, filters, reject loads, as well as the Gysel
combiners and the Gysel combiner reject loads. It is recom-
5-12
888-2365-001
Rev. B: 1/11/1999
WARNING: Disconnect primary power prior to servicing.
Summary of Contents for Platinum Series
Page 4: ......
Page 6: ......
Page 8: ...ii 888 2365 001 02 24 97 WARNING Disconnect primary power prior to servicing ...
Page 12: ...This page left blank intentionally ...
Page 22: ...1 10 888 2365 001 WARNING Disconnect primary power prior to servicing ...
Page 52: ...3 20 888 2365 001 Rev B 1 11 1999 WARNING Disconnect primary power prior to servicing ...
Page 62: ...4 10 888 2365 001 WARNING Disconnect primary power prior to servicing ...
Page 64: ...4 12 888 2365 001 WARNING Disconnect primary power prior to servicing ...
Page 66: ...4 14 888 2365 001 WARNING Disconnect primary power prior to servicing ...
Page 80: ...5 14 888 2365 001 Rev B 1 11 1999 WARNING Disconnect primary power prior to servicing ...