background image

19

APP-001f 

SEPT 2016

OPERATION

After the 10 minute STARTUP DELAY MODE is complete, 

the purger will enter its normal mode of COLLECTING 

AIR/WATER.

The foul gas that flows into the purger may carry a certain 

amount of condensed refrigerant, which is captured by 
the liquid drainer before it enters the purger’s condenser 
coil. From the liquid drainer, the liquid is fed directly into 
the low-pressure liquid return line. If this separation does 
not occur, liquid refrigerant will fill the purger’s condenser 
and limit the condensing capacity of the purger.

The liquid-free foul gas enters the purger condensing 

coil, which is submerged in the flooded evaporator. The 
refrigerant condenses inside the coil. The condensed 
refrigerant and noncondensible gas then flow through 
a check valve and into the air separator chamber. The 
condensed liquid refrigerant is removed from the high-
pressure air separator chamber through the liquid metering 
valve and to the low-pressure liquid return line.

Meanwhile, the noncondensible gas travels along the 
top of the air separator chamber and into the float ball 
chamber where it collects. As more noncondensible gases 
collect, the liquid level gradually falls, causing the float 
ball to fall. This changes the SPDT switch position of 
the liquid level float switch and energizes the purge gas 
solenoid valve (C) and the water bubbler fill line solenoid 
valve (D), allowing noncondensible gas to bleed through 
the orifice plate into the water bubbler. The Touchscreen 
indicates RELEASING AIR.  As air is released into the 
water bubbler, the liquid refrigerant level in the purger 
float ball chamber rises.

The control software operates each enabled remote 

purge point solenoid valve in sequence.  The control 
software energizes each purge point for 10 minutes.  If 
noncondensibles are released during this 10 minute period, 
then the control software will remain on that particular 
purge point for 10 additional minutes, for a total of 20 
minutes.  If noncondensibles are released during this 
second 10 minute period, then the control software will 
remain on that particular purge point for another 10 minutes, 
for a total of 30 minutes.  After a total of 30 minutes on one 
particular purge point, the control software will move to the 
next purge point, regardless of whether noncondensibles 
were released in the third 10 minute period.

The make-up liquid from the low-pressure pumped 

liquid line typically contains a small percentage of water 

dissolved in the liquid ammonia. This is the water the AUTO-
PURGER Plus will remove from the refrigeration system. 
Liquid ammonia and water are brought into the evaporator 
chamber of the purger, where the ammonia is evaporated 
and the water remains. Gradually the concentration of water 

in the evaporator chamber increases with time. When the 

concentration of water in the evaporator chamber reaches 
about 25% water for 10 continuous minutes, as detected 

by the water concentration sensor, the AUTO-PURGER 
Plus switches to the CONCENTRATING WATER mode. The 
purger stops collecting air, isolates the mixture of water 

and ammonia, and energizes the two electric heaters. 

SECTION 4   AUTO-PURGER PLUS OPERATION

The AUTO-PURGER Plus is designed to automatically 

startup and operate without the assistance of plant 
personnel. Beginning at start-up, the following is a 
description of the refrigerant flow through a purger when 
all connecting shut-off valves are open, see Figure 6.

START-UP

Make sure all piping, electrical connections, and settings 
are complete as described in this bulletin.

Models APPT08, APPT16, and APPT24 should have unused 
purge points disabled before start-up.  For example, an 

APPT08 that will only use 6 of the possible 8 purge points, 

should have purge points 7 and 8 disabled in the purger 
software. All purge points are enabled when shipped 
from the factory. To disable purge point, first energize the 
purger. Press the ‘Purge Point Enable’ button on Menu 
Screen 1. Then, touch the button of the purge point on the 
screen you wish to disable. If purge point is not shown 
on the screen, scroll up or down with \/ or /\ button to 
get to the purge point to disable and touch that button 
on the screen.

To start-up the APPT, open the foul gas, low-pressure 

pumped-liquid, low-pressure liquid return, and suction 
line shut-off valves. Open the purge gas valve. The water 
purge line shut-off valve should remain closed at this 
time (open only while draining water), see Figure 6.  On 
start-up, the AUTO-PURGER Plus enters a cooling down 
stage. The display indicates 3333 EVAP TEMP >40F (4C). 
In this stage, liquid refrigerant fills and cools the purger. 

The low-pressure pumped-liquid line solenoid valve (B) 

energizes to feed refrigerant to the low-pressure flooded 
evaporator. The liquid make-up level sensor, located in the 
evaporator chamber, senses when the flooded evaporator 

is full and closes the low-pressure pumped-liquid line 
solenoid valve (B).

At the same time the flooded evaporator is cooling, the 

control software energizes the first purge point solenoid 
valve. Foul gas enters the high-pressure air separator 
chamber and condenses to fill the high-pressure air 
separator chamber with liquid ammonia. When the float 
switch chamber fills with liquid refrigerant, the float ball 
rises and pulls in the float switch magnet. (If this chamber 

is already full of air, the float switch magnet will not pull-in 
until later when this air is released to the bubbler.)

After the evaporator shell temperature has cooled below 
40°F, the purger switches from the cooling down stage to 

STARTUP DELAY MODE for 10 minutes, as indicated by the 

Touchscreen no longer displaying 3333 EVAP TEMP>40F 

(4C), but instead displaying STARTUP DELAY MODE. The 
control software will not allow any noncondensibles to 

be released into the water bubbler until the 10 minute 

STARTUP DELAY MODE is complete. This 10 minute delay 

is necessary to give the purger time to condense enough 
foul gas to fill the high pressure air separator chamber 
with liquid ammonia.

continued on page 21 

TROUBLESHOOTING GUIDE 

 

On the touchscreen of the APPT there is a built-in troubleshoo>ng guide. This guide will show all the error messages 
displayed, what the error condi>on is, and a few condi>ons to check to fix the error state. This guide can be 
accessed in two ways, Menu Screen 3 has an op>on for Troubleshoo>ng Help. Pressing this op>on will bring you to 
the menu below where you can select which error condi>on you are looking for. 

 

O

 

  

O

 

 

The second way to access this guide is when you are in an error state there will be a buPon which will appear. 
Pressing that buPon which coincides with the error state the APPT currently is in will bring up the troubleshoo>ng 
sec>on for that par>cular error. 

 

The guide programmed into the touchscreen is the same guide which is following this sec>on in the product 
bulle>n. 

Summary of Contents for APPT08

Page 1: ...igerant noncondensible gas air and water purger for reducing the energy costs of operating an ammonia refrigeration system All models are preassembled pre wired insulated and include an automatic wate...

Page 2: ...nces only one point is effectively purged The best practice is to purge each condenser and receiver circuit separately It is extremely important to install purge points at locations sure to be liquid...

Page 3: ...pressor discharge main inlet Vertical condensers should be purged near the top of the vessel if possible For certain types of oil separators where very low velocities may exist near the top of the ves...

Page 4: ...quid ammonia that typically is also contaminated with water which is to be removed by the AUTO PURGER Plus The liquid line solenoid valve B on the AUTO PURGER Plus closes when the AUTO PURGER Plus is...

Page 5: ...ions to prevent injury or property damage ELECTRICAL CONNECTIONS The standard AUTO PURGER Plus requires a 115V 50 60Hz 17 amp electrical supply on a 20 amp circuit breaker models for 220V 50 60Hz 11 a...

Page 6: ...iquid drainer separates any liquid condensed in the purge point piping This liquid is fed to the low pressure liquid return line Therefore only foul gas no liquid enters the condensing section of the...

Page 7: ...d solenoid valve B to maintain the ammonia level in the evaporator shell b The low liquid level sensor prevents the electric heaters from energizing if no liquid is present which protects the heaters...

Page 8: ...lso used to exit back through menu mode Navigate up Navigate down ENTER To enter a speci c menu hierarchy or enter a parameter change Auto Purger Plus Technology Package Color Touchscreen Figure 6 O A...

Page 9: ...units for the display readout To change the selec on press or to switch the units Menu Screen 1 Air Purge Limit Purge Point Enable Water Collec on Display Units Air Purge Limit APPT can limit the amo...

Page 10: ...ctory con gured set up parameters Consult Hansen prior to aPemp ng to change parameters Menu Screen 2 Version Language Alarm History Setup Screen Version This menu contains information which can t be...

Page 11: ...hscreen as well as the color touchscreen but the touchscreen must be set to HMI Display Troubleshoo ng Help This menu allows the user to scroll through the error code messages for the APPT and read th...

Page 12: ...n the APPT are reading The units displayed will match what is selected in Menu Screen 1 Display Units Status Screen 1 Status Screen 2 Status Screen 3 STATUS SCREENS FOR APPT O Status screen 1 will pro...

Page 13: ...to give the Water Concentra on percentage Status Screen 4 Status Screen 5 Status Screen 6 O Status Screen 4 will provide the high side and low side pressure as recorded from the pressure transducers...

Page 14: ...7 provides the state of the level sensors and the oat switch O Status Screen 8 will provide the opera ng mode the purger is in and the ac ve purge point not applicable for APPC model Status Screen 7 S...

Page 15: ...he System Reset key has been pressed or power is cycled to the APPT while the Liquid Make Up Level Sensor is reading wet APPT will stay in this mode un l Liquid make Up Level Sensor goes dry This prev...

Page 16: ...ra ng water mode to indicate the temperature of the ammonia water solu on units will match the selected display units O READY TO DRAIN WATER OPEN WATER PURGE SHUT OFF VALVE THEN PRESS OK KEY appears w...

Page 17: ...ome to the screen below O nabled will stop the APPT from collec ng and saving the data to your storage device To remove the press the Remove Storage Device buPon When the dot turns green remove your a...

Page 18: ...e accessed in two ways Menu Screen 3 has an op on for Troubleshoo ng Help Pressing this op on will bring you to the menu below where you can select which error condi on you are looking for O O The sec...

Page 19: ...nutes as detected by the water concentration sensor the AUTO PURGER Plus switches to the CONCENTRATING WATER mode The purger stops collecting air isolates the mixture of water and ammonia and energize...

Page 20: ...ASSEMBLY CHAMBER HIGH SIDE TO LOW SIDE BYPASS VALVE NORMALLY CLOSED WITH ORIFICE PURGE VALVE WATER PURGE LINE SHUT OFF VALVE NO ORIFICE WATER PURGE LINE STRAINER NO ORIFICE FOUL GAS LINE LOW PRESSURE...

Page 21: ...n 10 psig 0 7 bar as detected by the low side pressure transducer the low side pressure assist solenoid valve F modulates to maintain 10 psig 0 7 bar in the evaporator chamber The concentrated water c...

Page 22: ...ill inhibit the water concentration mode of the purger The following components must be checked when the refrigerant oil is manually drained 1 Low liquid level sensor SPSN 1 2 Liquid level make up sen...

Page 23: ...ion line and shut off valves These should be a minimum size of On new installations also make sure the plastic shipping cap in suction line flange is removed Action Eliminate the restriction See also...

Page 24: ...Oil in purger Symptom No frost around the low side oil drain valve Action Remove oil through both the low side and high side drain valves See Figure 1 per safe refrigeration procedures See also the Ca...

Page 25: ...C Check Reconnect the PLC module s for the purge point solenoid coils Press the PURGE POINT ADV button to sequence through each purge point and verify the fuse does not blow If the fuse does blow that...

Page 26: ...Add vinegar to the bubbler water Then clean with the supplied brush Use a water conditioning housing and cartridge in the water supply line to the purger Refer to drawing 2003 07 for additional instru...

Page 27: ...enoid C D 70 1102 Kit Green Beacon Light solenoid B E F G ELECTRICAL 70 1088 Solenoid Coil DIN plug 115V 50 60 Hz 16 Watt 20 2428 Electric Heater 115V 50 60 Hz 750 Watt 20 2477 Electric Heater 230V 50...

Page 28: ...kW system or a 750 ton 2638 kW systemoperating below 0 psig 0bar g All models suitable for ammonia only SELECTING AN AUTO PURGER In addition to the AUTO PURGER AP Hansen Technologies offers three oth...

Reviews: