Status Screen 4 will provide the high side and low side pressure as recorded from the pressure transducers.
O
Status Screen 5 will tell which APPT solenoids are energized. This screen should match the beacon lights being on/
off on the solenoids (this screen doesn’t show purge point solenoids).
O
Status Screen 6 will tell if the heater is energized, the start up delay counter, and concentra>ng water reading. The
concentra>ng water reading is a raw number needing to be converted to give the Water Concentra>on percentage.
Status Screen 4
Status Screen 5
Status Screen 6
O
Status Screen 4 will provide the high side and low side pressure as recorded from the pressure transducers.
O
Status Screen 5 will tell which APPT solenoids are energized. This screen should match the beacon lights being on/
off on the solenoids (this screen doesn’t show purge point solenoids).
O
Status Screen 6 will tell if the heater is energized, the start up delay counter, and concentra>ng water reading. The
concentra>ng water reading is a raw number needing to be converted to give the Water Concentra>on percentage.
Status Screen 4
Status Screen 5
Status Screen 6
SECTION 3 COMPONENT DESCRIPTIONS
STATUS SCREENS FOR APPT
O
Status screen 1 will provide the number of >mes the purger went into a purge cycle and released either air or water
and the amount of minutes it spent during those purges.
O
Status screen 2 will provide the water concentra>on measurement for the flooded evaporator chamber of the APPT.
When the flooded evaporator chamber is empty this reading will be 60%. This value will not appear when
concentra>ng water mode is in effect.
O
Status screen 3 will provide the temperatures the thermocouples on the APPT are reading. The units displayed will
match what is selected in Menu Screen 1 – Display Units.
Status Screen 1
Status Screen 2
Status Screen 3
STATUS SCREENS FOR APPT
O
Status screen 1 will provide the number of >mes the purger went into a purge cycle and released either air or water
and the amount of minutes it spent during those purges.
O
Status screen 2 will provide the water concentra>on measurement for the flooded evaporator chamber of the APPT.
When the flooded evaporator chamber is empty this reading will be 60%. This value will not appear when
concentra>ng water mode is in effect.
O
Status screen 3 will provide the temperatures the thermocouples on the APPT are reading. The units displayed will
match what is selected in Menu Screen 1 – Display Units.
Status Screen 1
Status Screen 2
Status Screen 3
STATUS SCREENS FOR APPT
O
Status screen 1 will provide the number of >mes the purger went into a purge cycle and released either air or water
and the amount of minutes it spent during those purges.
O
Status screen 2 will provide the water concentra>on measurement for the flooded evaporator chamber of the APPT.
When the flooded evaporator chamber is empty this reading will be 60%. This value will not appear when
concentra>ng water mode is in effect.
O
Status screen 3 will provide the temperatures the thermocouples on the APPT are reading. The units displayed will
match what is selected in Menu Screen 1 – Display Units.
Status Screen 1
Status Screen 2
Status Screen 3
Status screen 1 will provide the number of times the purger went into a purge cycle and released either air or water and
the amount of minutes it spent during those purges.
Status screen 3 will provide the temperatures the thermocouples on the APPT are reading. The units displayed will
match what is selected in Menu Screen 1 – Display Units.
Status screen 2 will provide the water concentration measurement for the flooded evaporator chamber of the APPT.
When the flooded evaporator chamber is empty this reading will be 60%. This value will not appear when concentrating
water mode is in effect.
STATUS SCREENS FOR APPT