Hansen APPT08 Specifications, Applications, Service Instructions & Parts Download Page 24

24

APP-001f 
SEPT 2016

TOUCHSCREN DISPLAYS 7777

LOSS OF LOW-PRESSURE PUMPED-LIQUID.

 If the 

liquid line solenoid valve remains energized for more than 

30 minutes, it indicates there is insufficient low-pressure 

pumped-liquid available to maintain an adequate level in 

the flooded evaporator of the purger. The purger will not 

purge air until this is corrected.

REASON 1:

 Liquid line solenoid valve (B) is not opening 

or the seat/orifice is blocked.

Check:

 Make sure the liquid line solenoid valve (B) is 

energized. If not, check for voltage at the solenoid coil.

Action:

 Replace the coil if it is burned-out, otherwise 

clean or replace the valve. See also the Caution section 
on page 28.

REASON 2:

 Liquid line restricted.

Check:

 Look for closed shut-off valves in the pumped-

liquid line, plugged strainers, or the plastic shipping cap 

still in the liquid line flange.

Action:

 Inspect piping for a closed shut-off valve. Open 

the shut-off valves, clean the strainer, or remove the 
shipping cap. See also the Caution section on page 28.

NONCONDENSIBLES ARE NOT BEING 
RELEASED.

(See also page 23; 

Touchscreen displays 3333

)

REASON 1:

 Noncondensibles not present in system.

Check:

 Compare the refrigerant liquid temperature 

from condenser exit with the condensing pressure. The 
pressure/temperature relationship should be within 2 or 
3 psig (0.14 to 0.21 bar).

ACTION:

 None at this time.

REASON 2:

 Metering valve plugged.

Symptom:

 The purger appears to be operating properly, 

however, the low-pressure liquid-return line is not frosted.

Action:

 Fully open the metering valve to flush out any 

particles. Then, close the valve and reopen two turns.

REASON 3:

 Foul gas line is flooded with liquid.

Symptom:

 The bottom of the liquid drainer often remains 

frosted.

Check:

 Inspect condenser and foul gas piping. In many 

cases, the problem is liquid refrigerant being drawn from 

the purge point. To prevent this from happening, select 

purge point locations above liquid surfaces and make 

sure purge point lines are installed so that only vapor, and 

not liquid, can be drawn in. Refer to Piping Instructions 

in Section 2 of this bulletin.

Action:

 Correct condenser and foul gas piping.

AMMONIA INSTEAD OF NONCONDENSIBLES 

RELEASED FROM PURGER.

REASON 1:

 Purge gas solenoid valve (C) leaking at seat.

Symptom:

 A slow leak of noncondensibles to the bubbler.

Check:

 Look for dirt or a worn seat in the purge gas 

solenoid valve (C).

Action:

 Remove, clean, or replace the solenoid tube 

plunger or valve. See also the Caution section on page 28.

REASON 2:

 Oil in purger.

Symptom:

 No frost around the low side oil drain valve.

Action:

 Remove oil through both the low side and high 

side drain valves (See Figure 1) per safe refrigeration 
procedures. See also the Caution section on page 28.

REASON 3:

 Refrigeration compressors are stopped.

Symptom:

 After the refrigeration compressors are stopped, 

the purger releases ammonia into the water bubbler for 
about 1/2 hour until either the 2222 alarm or the 3333 
alarm is displayed.

Action:

 The purger should not be operated when the 

refrigeration compressors are stopped.  It is recommended 
to install a customer supplied, externally mounted, power 
relay to de-energize the purger when the refrigeration 
compressors are stopped.

WATER IS NOT BEING RELEASED

REASON 1:

 Water not present in system.

Check:

 Perform a water analysis of the vessel from which 

the low-pressure pumped liquid is supplied.  Divide ppm 
by 10,000 to convert to percent.

Action:

 None at this time.

REASON 2:

 The water concentration sensor is defective.

Check:

 Press the STATUS button on the Touchscreen 

and record the water solution percentage, the evaporator 

liquid temperature, and the low side pressure readings.  

Compare the evaporator liquid temperature with the low 
side pressure reading.  The water concentration sensor 
should read approximately 2% water for every 1 °F (0.6 

°C) that the evaporator liquid temperature is warmer than 

the temperature of pure saturated ammonia corresponding 
to the low side pressure reading.  The evaporator liquid 
temperature must be 12 °F (7 °C) warmer than the 
temperature of pure saturated ammonia corresponding to 
the low side pressure reading before the APPT will enter 

CONCENTRATING WATER mode.

Action:

 Replace the water concentration sensor if defective.

See also Caution section, page 28.

REASON 3:

 The low liquid level sensor is defective or 

out of calibration.

Check:

 The heaters will not energize, and the APPT will 

not release water, if the low liquid level sensor indicates 
no liquid is present.  Remove the cover of the electrical 
enclosure on the low liquid level sensor.  The red LED 
inside will be on if it senses liquid, and off if it senses 
gas.  If the sensor has frost where the sensor enters the 
vessel, but the red LED is off, the sensor may be defective.  
If there is no frost, either no liquid is present, or the 
sensor is logged with oil and the oil must be drained. To 
recalibrate, ensure liquid level is below level of sensor. 
Remove sensor housing cover and turn calibration screw 
clockwise slowly till LED illuminates. Then turn screw two 
full turns counterclockwise.

Action:

 Replace the low liquid level sensor if defective. 

See also Caution section, page 28.

SECTION 5 SERVICE, TROUBLESHOOTING, & PARTS

Summary of Contents for APPT08

Page 1: ...igerant noncondensible gas air and water purger for reducing the energy costs of operating an ammonia refrigeration system All models are preassembled pre wired insulated and include an automatic wate...

Page 2: ...nces only one point is effectively purged The best practice is to purge each condenser and receiver circuit separately It is extremely important to install purge points at locations sure to be liquid...

Page 3: ...pressor discharge main inlet Vertical condensers should be purged near the top of the vessel if possible For certain types of oil separators where very low velocities may exist near the top of the ves...

Page 4: ...quid ammonia that typically is also contaminated with water which is to be removed by the AUTO PURGER Plus The liquid line solenoid valve B on the AUTO PURGER Plus closes when the AUTO PURGER Plus is...

Page 5: ...ions to prevent injury or property damage ELECTRICAL CONNECTIONS The standard AUTO PURGER Plus requires a 115V 50 60Hz 17 amp electrical supply on a 20 amp circuit breaker models for 220V 50 60Hz 11 a...

Page 6: ...iquid drainer separates any liquid condensed in the purge point piping This liquid is fed to the low pressure liquid return line Therefore only foul gas no liquid enters the condensing section of the...

Page 7: ...d solenoid valve B to maintain the ammonia level in the evaporator shell b The low liquid level sensor prevents the electric heaters from energizing if no liquid is present which protects the heaters...

Page 8: ...lso used to exit back through menu mode Navigate up Navigate down ENTER To enter a speci c menu hierarchy or enter a parameter change Auto Purger Plus Technology Package Color Touchscreen Figure 6 O A...

Page 9: ...units for the display readout To change the selec on press or to switch the units Menu Screen 1 Air Purge Limit Purge Point Enable Water Collec on Display Units Air Purge Limit APPT can limit the amo...

Page 10: ...ctory con gured set up parameters Consult Hansen prior to aPemp ng to change parameters Menu Screen 2 Version Language Alarm History Setup Screen Version This menu contains information which can t be...

Page 11: ...hscreen as well as the color touchscreen but the touchscreen must be set to HMI Display Troubleshoo ng Help This menu allows the user to scroll through the error code messages for the APPT and read th...

Page 12: ...n the APPT are reading The units displayed will match what is selected in Menu Screen 1 Display Units Status Screen 1 Status Screen 2 Status Screen 3 STATUS SCREENS FOR APPT O Status screen 1 will pro...

Page 13: ...to give the Water Concentra on percentage Status Screen 4 Status Screen 5 Status Screen 6 O Status Screen 4 will provide the high side and low side pressure as recorded from the pressure transducers...

Page 14: ...7 provides the state of the level sensors and the oat switch O Status Screen 8 will provide the opera ng mode the purger is in and the ac ve purge point not applicable for APPC model Status Screen 7 S...

Page 15: ...he System Reset key has been pressed or power is cycled to the APPT while the Liquid Make Up Level Sensor is reading wet APPT will stay in this mode un l Liquid make Up Level Sensor goes dry This prev...

Page 16: ...ra ng water mode to indicate the temperature of the ammonia water solu on units will match the selected display units O READY TO DRAIN WATER OPEN WATER PURGE SHUT OFF VALVE THEN PRESS OK KEY appears w...

Page 17: ...ome to the screen below O nabled will stop the APPT from collec ng and saving the data to your storage device To remove the press the Remove Storage Device buPon When the dot turns green remove your a...

Page 18: ...e accessed in two ways Menu Screen 3 has an op on for Troubleshoo ng Help Pressing this op on will bring you to the menu below where you can select which error condi on you are looking for O O The sec...

Page 19: ...nutes as detected by the water concentration sensor the AUTO PURGER Plus switches to the CONCENTRATING WATER mode The purger stops collecting air isolates the mixture of water and ammonia and energize...

Page 20: ...ASSEMBLY CHAMBER HIGH SIDE TO LOW SIDE BYPASS VALVE NORMALLY CLOSED WITH ORIFICE PURGE VALVE WATER PURGE LINE SHUT OFF VALVE NO ORIFICE WATER PURGE LINE STRAINER NO ORIFICE FOUL GAS LINE LOW PRESSURE...

Page 21: ...n 10 psig 0 7 bar as detected by the low side pressure transducer the low side pressure assist solenoid valve F modulates to maintain 10 psig 0 7 bar in the evaporator chamber The concentrated water c...

Page 22: ...ill inhibit the water concentration mode of the purger The following components must be checked when the refrigerant oil is manually drained 1 Low liquid level sensor SPSN 1 2 Liquid level make up sen...

Page 23: ...ion line and shut off valves These should be a minimum size of On new installations also make sure the plastic shipping cap in suction line flange is removed Action Eliminate the restriction See also...

Page 24: ...Oil in purger Symptom No frost around the low side oil drain valve Action Remove oil through both the low side and high side drain valves See Figure 1 per safe refrigeration procedures See also the Ca...

Page 25: ...C Check Reconnect the PLC module s for the purge point solenoid coils Press the PURGE POINT ADV button to sequence through each purge point and verify the fuse does not blow If the fuse does blow that...

Page 26: ...Add vinegar to the bubbler water Then clean with the supplied brush Use a water conditioning housing and cartridge in the water supply line to the purger Refer to drawing 2003 07 for additional instru...

Page 27: ...enoid C D 70 1102 Kit Green Beacon Light solenoid B E F G ELECTRICAL 70 1088 Solenoid Coil DIN plug 115V 50 60 Hz 16 Watt 20 2428 Electric Heater 115V 50 60 Hz 750 Watt 20 2477 Electric Heater 230V 50...

Page 28: ...kW system or a 750 ton 2638 kW systemoperating below 0 psig 0bar g All models suitable for ammonia only SELECTING AN AUTO PURGER In addition to the AUTO PURGER AP Hansen Technologies offers three oth...

Reviews: