background image

5

APP-001f 

SEPT 2016

The clear tube of the water bubbler may become coated 

with mineral deposits after a period of time. These deposits 
can be removed by adding a cup of vinegar to the water 
in the bubbler and cleaning the clear tube through the top 
plastic fitting with the supplied brush. A water conditioning 
filter housing and cartridge are available for abnormally 

hard water.

WATER BUBBLER DRAIN LINE

A 1” (25 mm) PVC socket/1” FPT water drain connection 

is located at the bottom of the bubbler. The water bubbler 

drain line should flow to a suitable drain or container, see 
Figure 6. If the drain line is run overhead, the fitting on the 
top of the water bubbler must be sealed, including the ¼” 
NPT vent connection in the fitting, and a protective mesh 

installed around the clear tube. Do not run the line more 
than 10’ (3 m) above the height of the bubbler because 
the pressure on the water bubbler could be excessive. 

Support the drain line to prevent undue stress on the water 

bubbler. Also, do not install a shutoff valve in this line.

Initially, fill the water bubbler with water through the 3” 
(80 mm) plug located on top of the tube. Keep the plug 
lubricated and hand tight. Check for leaks at the hose 
fittings.

WATER PURGE LINE

Water removed from the refrigeration system by the 

AUTO-PURGER Plus flows out the water purge line. This 

line should be directed to a customer supplied container, 

such as a 55 gallon drum for example, see Figure 6. It is 
recommended to use rigid metal tubing or to secure the 

line. Commonly, when draining water, initially all the water 
is released, then any oil is released, and then a small 

quantity of ammonia vapor may be released. A loose hose 
may whip around when the last of the liquid slugs come 
out of the hose and is therefore not recommended. The 
customer supplied container may be partially filled with 
water, and the end of the water purge line submerged in 
this water so that any small amount of ammonia vapor 
that may be released is dissolved in this water.

OIL DRAINS

Excess oil can reduce the purger capacity by lowering 
the evaporating or condensing rate. Oil is not typically 
a problem. Oil in the evaporator chamber is typically 
released with the water that is released out the water purge 
line. However, any oil that may collect in the purger can 
be drained off through the two capped ¼” valves on the 
purger, see Figure 1.  Before draining oil, close the purge 
gas gauge valve to the water bubbler, the low-pressure 
pumped-liquid line shut-off valve, the foul gas line shut-
off valve, and the water bubbler fill line valve. Allow the 
purger to pump out, then close the low-pressure liquid 
return and suction line valves. Use normal oil draining 
precautions to prevent injury or property damage.

ELECTRICAL CONNECTIONS

The standard AUTO-PURGER Plus requires a 115V 50/60Hz 
17 amp electrical supply on a 20 amp circuit breaker; 

models for 220V 50/60Hz, 11 amps electrical supply on 
a 15 amp circuit breaker are available. All models have a 

½” (13 mm) knockout on the side of the control cabinet to 

access the power connection terminal strip.  

AUTO-PURGER Plus models APPT08, APPT16, and APPT24 

have an additional ¾” (20 mm) knockout for individual 
purge point solenoid valves. Wires from each purge point 

solenoid valve should be brought to the purger control 
cabinet. Any additional access holes should be made on 
the side of the control cabinet. All access holes into the 
control cabinet must be sealed to prevent moisture, dust, 
and debris entering the cabinet.

From each purge point solenoid, one wire is connected 
to the corresponding screw terminal for the purge point 
inside the control cabinet on the terminal strip. For 115V 
models, the other wire from the purge point solenoid is 
connected together for all the purge points and tied to 
the available neutral position on the top terminal strip. 
For the 220V models, the other wire from the purge point 
solenoid is connected together for all the purge points 
and tied to the top terminal strip labeled PP_COM.  Both 

115V and 220V models APPT08, APPT16, and APPT24 

supply 115V to the purge points.

All APPT models have a relay available which energizes 

whenever action is required by plant personnel. The 
normally open contacts will close when action is required. 
If desired, the contacts may be connected to a light, an 
audible alarm, or to a plant computer, to notify plant 
personnel to attend to the purger. The contacts are rated 
for 10 amps. Connection to the relay is made at the top 
terminal strip labeled REMOTE RELAY.

The purger should not be operated when the refrigeration 

compressors are stopped.  It is recommended to install  
a customer supplied, externally mounted, power relay to 
de-energize the purger when the refrigeration compressors 
are stopped.

After completing all electrical connections inside the 

cabinet, connect the cable from the Touchscreen to the 
PLC. Connect the cable plug to the socket and tighten the 

hand screws. Refer to the wiring tag inside unit.

LEAK TEST

Use standard refrigeration procedures to check the 

AUTO-PURGER Plus for leaks before placing it in service. 

To confirm a leak-free AUTO-PURGER Plus, manually 

open one remote purge point solenoid valve, if there is 
one. Manually open the foul gas shut-off valve and allow 
pressure inside the purger to build to condensing pressure, 
as shown on the high side pressure gauge. Then, manually 
open the high side to low side bypass valve to pressurize 
the evaporator section of the purger, as shown on the low 
side pressure gauge, see Figure 6. Check for leaks. Close 
the high side to low side bypass valve.

SECTION 2   INSTALLATION

Summary of Contents for APPT08

Page 1: ...igerant noncondensible gas air and water purger for reducing the energy costs of operating an ammonia refrigeration system All models are preassembled pre wired insulated and include an automatic wate...

Page 2: ...nces only one point is effectively purged The best practice is to purge each condenser and receiver circuit separately It is extremely important to install purge points at locations sure to be liquid...

Page 3: ...pressor discharge main inlet Vertical condensers should be purged near the top of the vessel if possible For certain types of oil separators where very low velocities may exist near the top of the ves...

Page 4: ...quid ammonia that typically is also contaminated with water which is to be removed by the AUTO PURGER Plus The liquid line solenoid valve B on the AUTO PURGER Plus closes when the AUTO PURGER Plus is...

Page 5: ...ions to prevent injury or property damage ELECTRICAL CONNECTIONS The standard AUTO PURGER Plus requires a 115V 50 60Hz 17 amp electrical supply on a 20 amp circuit breaker models for 220V 50 60Hz 11 a...

Page 6: ...iquid drainer separates any liquid condensed in the purge point piping This liquid is fed to the low pressure liquid return line Therefore only foul gas no liquid enters the condensing section of the...

Page 7: ...d solenoid valve B to maintain the ammonia level in the evaporator shell b The low liquid level sensor prevents the electric heaters from energizing if no liquid is present which protects the heaters...

Page 8: ...lso used to exit back through menu mode Navigate up Navigate down ENTER To enter a speci c menu hierarchy or enter a parameter change Auto Purger Plus Technology Package Color Touchscreen Figure 6 O A...

Page 9: ...units for the display readout To change the selec on press or to switch the units Menu Screen 1 Air Purge Limit Purge Point Enable Water Collec on Display Units Air Purge Limit APPT can limit the amo...

Page 10: ...ctory con gured set up parameters Consult Hansen prior to aPemp ng to change parameters Menu Screen 2 Version Language Alarm History Setup Screen Version This menu contains information which can t be...

Page 11: ...hscreen as well as the color touchscreen but the touchscreen must be set to HMI Display Troubleshoo ng Help This menu allows the user to scroll through the error code messages for the APPT and read th...

Page 12: ...n the APPT are reading The units displayed will match what is selected in Menu Screen 1 Display Units Status Screen 1 Status Screen 2 Status Screen 3 STATUS SCREENS FOR APPT O Status screen 1 will pro...

Page 13: ...to give the Water Concentra on percentage Status Screen 4 Status Screen 5 Status Screen 6 O Status Screen 4 will provide the high side and low side pressure as recorded from the pressure transducers...

Page 14: ...7 provides the state of the level sensors and the oat switch O Status Screen 8 will provide the opera ng mode the purger is in and the ac ve purge point not applicable for APPC model Status Screen 7 S...

Page 15: ...he System Reset key has been pressed or power is cycled to the APPT while the Liquid Make Up Level Sensor is reading wet APPT will stay in this mode un l Liquid make Up Level Sensor goes dry This prev...

Page 16: ...ra ng water mode to indicate the temperature of the ammonia water solu on units will match the selected display units O READY TO DRAIN WATER OPEN WATER PURGE SHUT OFF VALVE THEN PRESS OK KEY appears w...

Page 17: ...ome to the screen below O nabled will stop the APPT from collec ng and saving the data to your storage device To remove the press the Remove Storage Device buPon When the dot turns green remove your a...

Page 18: ...e accessed in two ways Menu Screen 3 has an op on for Troubleshoo ng Help Pressing this op on will bring you to the menu below where you can select which error condi on you are looking for O O The sec...

Page 19: ...nutes as detected by the water concentration sensor the AUTO PURGER Plus switches to the CONCENTRATING WATER mode The purger stops collecting air isolates the mixture of water and ammonia and energize...

Page 20: ...ASSEMBLY CHAMBER HIGH SIDE TO LOW SIDE BYPASS VALVE NORMALLY CLOSED WITH ORIFICE PURGE VALVE WATER PURGE LINE SHUT OFF VALVE NO ORIFICE WATER PURGE LINE STRAINER NO ORIFICE FOUL GAS LINE LOW PRESSURE...

Page 21: ...n 10 psig 0 7 bar as detected by the low side pressure transducer the low side pressure assist solenoid valve F modulates to maintain 10 psig 0 7 bar in the evaporator chamber The concentrated water c...

Page 22: ...ill inhibit the water concentration mode of the purger The following components must be checked when the refrigerant oil is manually drained 1 Low liquid level sensor SPSN 1 2 Liquid level make up sen...

Page 23: ...ion line and shut off valves These should be a minimum size of On new installations also make sure the plastic shipping cap in suction line flange is removed Action Eliminate the restriction See also...

Page 24: ...Oil in purger Symptom No frost around the low side oil drain valve Action Remove oil through both the low side and high side drain valves See Figure 1 per safe refrigeration procedures See also the Ca...

Page 25: ...C Check Reconnect the PLC module s for the purge point solenoid coils Press the PURGE POINT ADV button to sequence through each purge point and verify the fuse does not blow If the fuse does blow that...

Page 26: ...Add vinegar to the bubbler water Then clean with the supplied brush Use a water conditioning housing and cartridge in the water supply line to the purger Refer to drawing 2003 07 for additional instru...

Page 27: ...enoid C D 70 1102 Kit Green Beacon Light solenoid B E F G ELECTRICAL 70 1088 Solenoid Coil DIN plug 115V 50 60 Hz 16 Watt 20 2428 Electric Heater 115V 50 60 Hz 750 Watt 20 2477 Electric Heater 230V 50...

Page 28: ...kW system or a 750 ton 2638 kW systemoperating below 0 psig 0bar g All models suitable for ammonia only SELECTING AN AUTO PURGER In addition to the AUTO PURGER AP Hansen Technologies offers three oth...

Reviews: