5.4.4 Parameter window “X: preset”
Fig. 5.7 parameter window “X: preset”
It is able set the brightness value in “X: preset” shown in Fig. 5.7. There are two preset objects per output:
“preset 1” and “preset 2” which are used to realize the lighting control. It is also able to save the current brightness
status as the new preset value. These 2 preset values have the same parameters setup, so here take one as an
example.
Parameter “Active preset 1 via bus telegram”
This parameter is used to activate preset 1.Options:
Active
Deactive
It will not activate the preset 1 with “Deactive”, and show the following parameter with “Active”.
Parameter “Brightness value is”
This parameter defines the time when starting the dimming by “preset 1”, and there is 1 bit data to control “X
preset 1”: “0” and “1”, which is able to call 2 different brightness values. Options:
Dimming on
Switching on softly
When select “dimming on”, the dimming time of object “X preset 1” is the input time of “Time duration of
dimming Time =entry” multiplied by 2; When select “switching on softly”, the dimming time of “X preset1” is
the default value: 4 seconds.
Parameter “Brightness value at obj=0(1%~100%)”
This parameter defines the brightness value when receiving “0” by “X preset 1”.Option:
1~100%
Parameter “Brightness value at obj=1(1%~100%)”
This parameter defines the brightness value when receiving “1” by “X preset 1”.Option: