K-BUS
®
KNX/EIB
Dimming Actuators
28
7
LEDs of indicating output status for each channel, LED on meaning the channel has output, or else no output
8
LED1~LED4, indicating output current of a channel increased by 350mA
9
Manual buttons, switch via short operation, relative dimming via long operation (no telegram)
10
KEY1~KEY4, switch current button for a channel, setting output current
11
Input terminals, input voltage 12~48V DC
Manually set the output current is described as follows:
Switching current button for a channel
: set output current for the channel, if the button (KEY1~KEY4) is
on, the output current of the channel is increased by 350mA and its LED (LED1~LED4) is on; if the button is off,
the current is not increased and the LED is off.
Switching current button for all channels
: set output current for all channels, if the button (KEY5) is on,
the output current of all channels is increased by 350mA and its LED(LED5) is on; if the button is off, the current
are not increased and the LED is off.
The button that set the output current is a dial switch, when it is toggled down, the button is on and the
corresponding LED is also on; when it is toggled up, the button is off and the corresponding LED is also off.
The corresponding output, dial switch and LED for each channel are as follows:
Table 1
Channel
Output
Switching current button
Indicate LED
A
A1, A2
KEY1
LED1
B
B1, B2
KEY2
LED2
C
C1, C2
KEY3
LED3
D
D1, D2
KEY4
LED4
Specific output current for each channel is controlled as shown in the table below:
Table 2
Output
Output 350mA
Output 700mA
Output 1A
A1, A2
KEY5 off, LED5 off
KEY1 off, LED1 off
KEY5 off, LED5 off
KEY1 on, LED1 on
or
KEY5 on, LED5 on
KEY1 off, LED1 off
KEY5 on, LED5 on
KEY1 on, LED1 on
B1, B2
KEY5 off, LED5 off
KEY2 off, LED2 off
KEY5 off, LED5 off
KEY2 on, LED2 on
or
KEY5 on, LED5 on
KEY2 off, LED2 off
KEY5 on, LED5 on
KEY1 on, LED1 on