Installation of generator
Installation of dual-bearing generators (BG 132)
Assembly
Ö
Fig. 19, Assembly of flange mount
(dual-bearing, BG 132 model with reinforced bearing plate), page 60
>
Apply Loctite to the screw thread of the four screws
[2a]
and place
a toothed washer
[2b]
underneath the screw.
>
Place the flange
[1]
onto the generator and secure with four screws
[2a]
to
a tightening torque of 75 Nm.
>
Mount the coupling plate
[3]
on the shaft at the generator and prevent it
from twisting on the shaft with a key.
>
Secure the drive side of the coupling
[4]
to the drive and insert it into the
coupling plate. If necessary, while inserting, twist slightly until the gearing
locks.
>
Secure the flange
[1]
to the drive unit.
1
4x
2a
2b
3
4
2a
M12 x 40 DIN 933
2b
VH12 DIN 128
Fig. 19 Assembly of flange mount
(dual-bearing, BG 132 model with reinforced bearing plate)