Issue 05/2013
Page 80
Operation
Operating conditions
7.2
Operating conditions
The generator may only be used if the following operating conditions
are met.
y
Only connect devices which have voltage and frequency data on their
rating plate matching that for the power generation system. The total
power draw of all connected units must not exceed the output indicated
for the current power generation system. Only connect as many units
as the generator output can supply sufficiently. Do not overload the
generator.
y
A cooling air feed above 40 °C can lead to power restrictions; in extreme
cases it can cause damage to the generator. The temperature of the
supplied cooling air should not exceed 40 °C. Observe the necessary
minimum clearances. The generator must have an unobstructed flow of
cooling air and an unhindered cooling air discharge.
If the generator is not sufficiently cooled, or in conditions which deviate
from the permissible operating conditions, the output voltage of the
generator will be reduced automatically. To prevent damage to connected
devices, in this case it will be necessary to reduce the output connected to
the generator.