Installation of generator
Electrical generator connection
6.9
Electrical generator connection
Carefully read the safety instructions before installing, commissioning
and operating the generator, and follow the instructions and heed the
information.
Ö
General safety instructions, installation, page 28
This section is only relevant for generators that are not fitted with a switch
box in the factory.
Danger
Risk of injury and risk of damage!
y
Incorrect installation of the generator can lead to
malfunctioning, damage or danger.
►
Before the installation of the generator read this operating
manual completely and carefully.
►
The assembly / disassembly of generator as well as the
maintenance, service and replacement work may only be
carried out by authorised and qualified technicians.
►
Only use the generator according to the information in the
operating manual and the purposes indicated in the section
on “intended use”.
Danger
Danger to life through electric shock
y
A grounding of the neutral conductor of the generator
(N, neutral conductor) invalidates the “electrical separation”
protective measure.
►
Never ground the neutral conductor of the generator.
Only authorised persons may carry out connection and assembly of work
on electrical installations, according to applicable national requirements (in
Germany: these include VDE specifications).
If the neutral conductor N is earthed despite this, the work may be carried
out by a qualified electrician. A fault current (FI) protective switch must be
downstream of the generator output. Carry out suitable measurements to
verify the effectiveness of the electrical safety measures.