Sy
nch
ro
no
us g
en
er
at
or
s o
f s
er
ie
s D
G
G
, D
W
G a
nd W
G
Issue 05/2013
Page 38
Installation of generator
Installation of single-bearing generators
6.6.2
Installation dimensions
Generator dimension
The generators vary according to the output and model.
IF needed, request the drawing for your generator from
Generator.Technik.Systeme GmbH & Co. KG.
Important
►
Do not attach any third party parts to
the mounting profiles on the generator
housing.
6.6.3
Minimum clearances and cooling provisions
y
The generator needs sufficient ventilation for cooling. The cooling air is
drawn through the cooling profiles by the fan wheel on the rear side of the
generator and across the housing, towards the front side.
y
Ensure adequate air feed and exhaust openings.
y
Comply with the following minimum clearances and note the regulations
for cooling.
Minimum clearances
When installing, respect the following minimum
clearances from fixed parts or walls.
Ö
adjacent figures
y
On the side and top: a = 100 mm
y
Rear: b = 170 mm
In individual cases, the clearances may vary
from these figures. Get in touch with
Generator.Technik.Systeme GmbH & Co. KG.
b
b
a
a
a