English (GB)
5
1.3.3 Pump performance
Performance data at maximum pump counter-pressure
* Observe the maximum permissible temperatures and that the friction loss increases with the viscosity of the dosing medium.
** The maximum dosing flow of HV-variant pumps is up to 10 % lower.
1.3.4 Accuracy
• Applies to:
– water as dosing medium
– fully deaerated dosing head
– standard pump version.
• Dosing flow fluctuation and linearity deviation: ± 1.5 % of the
full-scale value.
• Construction tolerance: according to VDMA 24284.
1.3.5 Inlet pressure and counter-pressure / suction lift during
operation
Maximum inlet pressure
* For pumps with pressure sensor (Flow Monitor pump option),
the inlet pressure on the suction side must not exceed 1 bar.
Minimum counter-pressure at the pump discharge valve
* For pumps with pressure sensor (Flow Monitor pump option),
the minimum system pressure is 2 bar and the minimum
pressure difference between the suction and discharge sides
is 2 bar. If the volume flow is not constant (as, for example, in
the case of contact or analog control), even small volume
flows should not fall below the minimum pressure or the
minimum pressure difference.
Maximum suction lift* (start-up) for media with a viscosity
similar to water
* Deaeration valve open.
Maximum suction lift* (continuous operation) for
non-degassing media with a viscosity similar to water
* Dosing head and valves filled with dosing medium.
1.3.6 Sound pressure level
65 dB(A), testing according to DIN 45635-01-KL3.
1.3.7 Enclosure class
• Pump with mains plug: IP65.
• Pump without mains plug: IP65 can only be ensured if the
power supply cable is connected with IP65 protection.
1.3.8 Required energy
Power supply for AC voltage
• Rated voltage range: 110-240 V.
Deviation from the rated value: ± 10 %.
• Mains frequency: 50/60 Hz.
• Maximum power consumption: 70 W including all sensors
(reduced input power according to pump type and connected
sensors).
Pump type
Normal operation
Slow-mode operation
Slow-mode-2 operation
Q**
p max.*
Max. stroke rate
Q**
p max.*
Max. stroke rate
Q**
p max.*
Max. stroke rate
[l/h]
[bar]
[n/min]
[l/h]
[bar]
[n/min]
[l/h]
[bar]
[n/min]
DDI 60-10
60
10
180
40
10
120
24.7
10
74
DDI 150-4
150
4
180
100
4
120
62
4
74
Note
The pump can be operated in the range between
0.125 % and 100 % of the maximum dosing capacity.
Note
The maximum display indication is higher than the
nominal capacity of the pump because it refers to the
default setting.
Pump type
Operating conditions / version
All*
[bar]
DDI 60-10 - DDI 150-4
2
Pump type
Operating conditions / version
All*
[bar]
DDI 60-10 - DDI 150-4
1
Pump type
Operating conditions / version
Continuous operation
[m]
DDI 60-10 - DDI 150-4
1
Pump type
Operating conditions / version
Normal operation
[m]
DDI 60-10
6
DDI 150-4
3
Caution
The enclosure class is only met if the sockets are
protected! The data regarding the enclosure class
applies to pumps with correctly inserted plugs or
screwed-on caps.
Note
The power supply must be electrically isolated from
the signal inputs and outputs.