Control unit
23 | 80
BA_TD
3-
BM
000e
n_
06
4_sof
tli
Q
-M
C
.docx
Menu items
Settings/remarks
Water volumes
Soft water exchanger 1 [m³]
Soft water exchanger 2 [m³]
Raw water blending [m³]
Make-up volume [l]
Soft water
sample
Exchanger 1
0 – Factory setting
1 – Carry out function
Exchanger 2
0 – Factory setting
1 – Carry out function
Perform soft water sampling for selected exchanger. After completion,
the factory setting is activated again.
Find reference
position
regeneration
valve
Regeneration
valve exchanger 1
0 – Factory setting
1 – Carry out function
Regeneration
valve exchanger 2
0 – Factory setting
1 – Carry out function
Move to reference position of the selected exchanger. Ongoing
regenerations are aborted. After completion, the factory setting is
activated again.
Fill operating
water volume
into brine tank
Deactivated – factory setting
Activated – Carry out function
Fill the brine tank to a minimum water level (e.g. after cleaning the brine
tank). After completion, the factory setting is activated again.
Start test
regeneration
0 – Factory setting
both – both control valves in succession
2 – only exchanger 2
1 – only exchanger 1
Select
regeneration
time
Automatic
Factory setting
Fixed
Programming of 1 – 3 fixed regeneration times.
Regeneration only takes place, if required.
Weekly timer
regeneration time
1/2/3
Mon ... Sun
Time of the regeneration on each day of the week
(factory setting: Mon – Fri at 7:00 am)
Inputs and
outputs
Voltage-free
contact function
Regeneration water delivery pump (factory setting)
Contact closed during the regeneration steps
salting, slow rinse, backwash and washing out.
This setting must be made in connection with the
regeneration water delivery pump available as an
accessory (refer to chapter 3.6).
Regeneration message
Contact closed during the entire regeneration.
Summary of Contents for softliQ:MC