Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION
47
B2)
R410A refrigerant system
Total rated capacity of downsteam indoor units: X(Btu/h)
Model
Y-type branch
X≤48500
FQ01A/A
5.7 Piping size between mode exchanger and downstream indoor unit (b,
c, d, g)
Rated capacity of indoor unit
C(Btu/h)
Pipe between mode exchanger and IDU
Gas Pipe mm(inch)
Liquid Pipe mm(inch)
C≤9500
Φ9.52(3/8)
Φ6.35(1/4)
9500
<
C≤17100
Φ12.7(1/2)
Φ6.35(1/4)
17100
<
C≤48500
Φ15.9(5/8)
Φ9.52(3/8)
5.8 Piping between indoor branch and indoor unit (e, f, i, j, k)
Size of connection pipe between indoor branch and indoor unit should be consistent with the
connection pipe of indoor unit.
Rated capacity of indoor units:
X ((Btu/h)
Size of connection pipe between indoor branch and indoor unit
Gas pip mm(inch)
Liquid pipe mm(inch)
C≤9500
Φ9.52(3/8)
Φ6.35(1/4)
9500
<
C≤17100
Φ12.7(1/2)
Φ6.35(1/4)
17100
<
C≤48500
Φ15.9(5/8)
Φ9.52(3/8)
5.9 Pipe size between indoor branches
(“I”)
Rated capacity of indoor units:
X ((Btu/h)
Size of connection pipe between indoor branch and indoor unit
Gas pipe mm(inch)
Liquid pipe mm(inch)
X≤9500
Φ9.52(3/8)
Φ6.35(1/4)
9500
<
X≤17100
Φ12.7(1/2)
Φ6.35(1/4)
17100
<
X≤48500
Φ15.9(5/8)
Φ9.52(3/8)
5.10 Connection method when capacity of indoor unit exceeds 48500
Btu/h
When connecting to the indoor unit with capacity of over 48500 Btu/h, it is not allowed to connect
with only one branch; it must use two branches controlled by the same main board for parallel
connection.
Parallel connection
Indoor unit communication
connection for mode exchanger
Remarks
Indoor unit No.1 and No.2
―1D1 1D2‖
Parallel connection can be conducted
only as the combination of this table, it
is not allowed to otherwise connect.
Note that after the connection,
manually set the SA2 dial code of
corresponding mainboard, and dial the
code in the first place to number end.
Indoor unit No.3 and No.4
―3D1 3D2‖
Indoor unit No.5 and No.6
―5D1 5D2‖
Indoor unit No.7 and No.8
―7D1 7D2‖
Summary of Contents for Ultra Heat GMV-VQ72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Recovery Series ...
Page 30: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 26 ...
Page 73: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 69 ...
Page 135: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 131 ...
Page 203: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 199 5 4 NCHS4B U ...
Page 205: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 201 5 5 NCHS8B U ...
Page 207: ...Jf00303410 ...