Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial COMMISSIONING OPERATION
94
(LED3). The master unit is displayed as follows:
LED1
LED2
LED3
Function Code
Display Mode
Confirmation
Display Mode
Current Data
Display Mode
A8
On
/
/
OF
Blinking
A8
On
/
/
On
Blinking
Next, if
―On‖ data is selected, then press "SW4" to confirm it. The master unit is displayed as
follows:
LED1
LED2
LED3
Function Code
Display Mode
Confirmation
Display Mode
Current Data
Display Mode
A8
On
=
On
On
On
Note: other CU function‘s setting way is the same with ―A8‖. ―/‖ means nothing displayed.
On the master unit, press "SW5" to return to the upper level if there are two levels of menu. And
press "SW5" long to cancel the setting function status.
Step 6: When
―DI‖ function displays, press "SW4" on the master unit, then the master unit is
displayed as follows:
LED1
LED2
LED3
Function Code
Display Mode
Confirmation
Display Mode
Current Data
Display Mode
NH
Blinking
/
/
Parameter value
On
Then users can select corresponding functions by pressing "SW1" on the master unit, including:
LED1
LED2
LED3
Function Code
Display Mode
Confirmation
Display Mode
Current Data
Display Mode
NH
Blinking
/
/
Parameter value
On
NP
Blinking
/
/
Parameter value
On
NW
Blinking
/
/
Parameter value
On
PL
Blinking
/
/
Parameter value
On
PM
Blinking
/
/
Parameter value
On
PH
Blinking
/
/
Parameter value
On
N1
Blinking
/
/
Parameter value
On
N9
Blinking
/
/
Parameter value
On
LED3 displays the parameter value. By default, the ODU temperature values unit are
℃
, and
pressure values unit are 0.01MPa.
For example:
Parameter Code
Parameter Name
Unit
Remark
NH
Suction temperature
°C
If LED3 shows 12, it means suction temperature is 12
℃
.
NP
Discharge temperature
°C
If LED2 shows 1 and LED3 shows 04, it means discharge
temperature is 104
℃
.
NW
Environment temperature
°C
If LED2 shows - and LED3 shows 10, it means
environment temperature is -10
℃
.
PL
Low pressure
0.01MPa
If LED3 shows 95, it means low pressure is 0.95MPa.
PM
Middle pressure
0.01MPa
Summary of Contents for Ultra Heat GMV-VQ72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Recovery Series ...
Page 30: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 26 ...
Page 73: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 69 ...
Page 135: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 131 ...
Page 203: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 199 5 4 NCHS4B U ...
Page 205: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 201 5 5 NCHS8B U ...
Page 207: ...Jf00303410 ...