Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION
48
Connecting method is shown as in the Fig.23.
1) Branch selection of indoor unit of mode exchanger (
―C1‖)
R410A refrigerant system
Total rated capacity of downstream
indoor units: X(Btu/h)
Model
Y-type branch
48500<
X≤96000
FQ01B/A
2) Pipe size between mode exchanger and downstream
and indoor unit (―m‖)
Rated capacity of indoor
units: X ((Btu/h)
Size of connection pipe between indoor branch and indoor unit
Gas pipe mm(inch)
Liquid pipe mm(inch)
48500
<
X≤72000
Φ19.05(3/4)
Φ9.52(3/8)
72000
<
X≤96000
Φ22.2(7/8)
Φ9.52(3/8)