Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial COMMISSIONING OPERATION
108
Code
Display
status
Code
Display
status
Code
Display
status
07_Detect
indoor
components
XXXX/
Error
code
Light
System detects error on indoor
components. XXXX means the
project code of IDU with error. 3s
later, related error code will be
displayed.
Elimination methods of above errors can be found in Troubleshooting.
Step 13: Progress 08
is ―Confirm preheated compressor‖.
At first, make sure that the ODU valves connecting with IDU are opening. Main board will display:
——
Debugging code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display status
Code
Display status
Code
Display status
08_Confirm preheated
compressor
db
Light
08
Light
on
Light
If the ODU valves connecting with IDU have been opened manually, then press SW4 confirmation
button on the master unit to confirm it.
If ODU compressors have been preheated for more than 8h, system will display as below and start
next progress.
——
Debugging code
Progress code
Status code
progress
LED1
LED2
LED3
Code
Display status
code
Display status
Code
Display status
08_Confirm preheated
compressor
db
Light
08
Light
oC
Light
If less than 8h of preheat time is detected, system will give error alarm and display as below. Then
press SW4 confirmation button and SW2 button at the same time to skip the wait time and start next
progress. But this will cause force start of the compressor, which may damage the compressor.
——
Debugging code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display status
Code
Display status
Code
Display status
08_Confirm preheated
compressor
db
Light
08
Light
U0/
Preheat
time
Blink
Step 14: Progress 09
is ―Refrigerant judgments before startup‖.
If the refrigerant quantity inside the system meets the requirement of operation startup, system will
display as below and start next progress.
——
Debugging code
Progress code
Status code
progress
LED1
LED2
LED3
Code
Display status
code
Display status
Code
Display status
09_Refrigerant
judgments before
startup
db
Light
09
Light
oC
Light
If there‘s no or not enough refrigerant in the system to meet the requirement of operation startup,
system will display U4 ―refrigerant shortage protection‖ and fails to start next progress. Then check if
there‘s any leakage or add refrigerant inside until error eliminates.
Summary of Contents for Ultra Heat GMV-VQ72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Recovery Series ...
Page 30: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 26 ...
Page 73: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 69 ...
Page 135: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 131 ...
Page 203: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 199 5 4 NCHS4B U ...
Page 205: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 201 5 5 NCHS8B U ...
Page 207: ...Jf00303410 ...