Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial COMMISSIONING OPERATION
104
05_Internal
communication
detection
C2
Light
Communication between master
ODU and inverter compressor
driver has error.
C0
Light
Communication between master
ODU and IDUs has error.
db
Light
05
Light
oC
Light
System detection is done. Next
step will start automatically.
06_Detect
outdoor
components
Error
code
Light
System detects that outdoor
components have error.
db
Light
06
Light
oC
Light
System detects no error on outdoor
components. Next step will start
automatically.
07_Detect
indoor
components
XXXX/
Error
code
Light
System detects error on indoor
components. XXXX means the
project code of IDU with error. 3s
later, related error code will be
displayed.
db
Light
07
Light
oC
Light
System detects no error on indoor
components. Next step will start
automatically.
08_Confirm
preheated
compressor
db
Light
08
Light
on
Light
LED3 displays the on-off state of
ODU valves connecting with IDU.
In this case, please confirm if the
ODU valves are open manually.
db
Light
08
Light
U0/
Preheat
time
Blink
U0 means preheat time for
compressor is less than 8 hours.
db
Light
08
Light
oC
Light
Compressor has been preheated
for 8 hours. Next step will start
automatically.
09_Refrigerant
judgments
before startup
U4
Light
System is lack of refrigerant.
db
Light
09
Light
oC
Light
Refrigerant is normal. Next step will
start automatically.
10_
——
——
——
——
——
——
No meaning.
11_
——
——
——
——
——
——
No meaning.
12_Confirm
debugging
startup
db
Light
12
Light
AE
Blink
Ready for units to start debugging.
db
Light
12
Light
oC
Light
The unit starts up in the status of
manual calculation of refrigerant
charging amount.
13_
——
——
——
——
——
——
No meaning.
14_
——
——
——
——
——
——
No meaning.
15_Cooling
debugging
db
Light
15
Light
UC
Light
Debugging for cooling mode.
(Debugging operation mode, the
system will select automatically
with no need of manual setting).
Error
code
Light
Malfunction occurs when
debugging for cooling mode.
16_Heating
debugging
db
Light
16
Light
UH
Light
Debugging for heating mode.
(Debugging operation mode, the
system will select automatically
with no need of manual setting).
Error
code
Light
Malfunction occurs when
debugging for heating mode.
Summary of Contents for Ultra Heat GMV-VQ72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Recovery Series ...
Page 30: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 26 ...
Page 73: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 69 ...
Page 135: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 131 ...
Page 203: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 199 5 4 NCHS4B U ...
Page 205: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 201 5 5 NCHS8B U ...
Page 207: ...Jf00303410 ...