Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE
147
For inverter compressors, current will be deviated 10% while rate of turn and operating condition vary.
(1) For inverter compressors QXAW-F518zX440B:
The figures below shows cooling capacity curves, and input power curves, and refrigerant flow rate
curves, which are obtained in the testing condition that suction temperature is 35
℃
, and liquid subcooled
temperature is 8.3
℃
, and ambient temperature is 35
℃
.
NOTE: You can infer from the preceding figures the current of the compressors operating at other
frequency bands.
Step 2:
Check whether the compressor sounds sharp or rubs. Compare the sound of the faulty
compressor with that of normal ones.