Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial UNIT INTRODUCTION
14
3.2 C&H Mode Exchanger
C&H Mode Exchanger is used for connecting outdoor unit and indoor unit, and providing high
pressure, low pressure and medium pressure refrigerant provided by outdoor unit for cooling or heating
mode and complete the refrigerant system circulation for the purpose of adjusting indoor temperature.
(1) C&H Mode Exchanger provides multiple branch combination forms, which can connect different
kinds of lower branches. Each branch of the C&H Mode Exchanger can connect 8 indoor units at the
most and the total capacity should be no more than 14kw.
(2) C&H Mode Exchanger provides multiple branches used for connection lower indoor units. It‘s
convenient for installation, leakage detection and maintenance.
(3) C&H Mode Exchanger is supplied power independently, which connects indoor unit and outdoor unit
with communication wire. It‘s convenient and flexible for installation and construction.
One-to-one Mode Exchanger NCHS1B(U)
One-to-two Mode Exchanger NCHS2B(U)
One-to-four Mode Exchanger NCHS4B(U)
One-to-eight Mode Exchanger NCHS8B(U)
Summary of Contents for Ultra Heat GMV-VQ72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Recovery Series ...
Page 30: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 26 ...
Page 73: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 69 ...
Page 135: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 131 ...
Page 203: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 199 5 4 NCHS4B U ...
Page 205: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 201 5 5 NCHS8B U ...
Page 207: ...Jf00303410 ...