Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial COMMISSIONING OPERATION
106
According to the above errors, reset the master unit (Set master unit S7 as
―00‖; Set slave unit S7
as
―10‖), then start debugging again.
Step 7: Progress 02 is allocating addresses. If allocating addresses is done, then main board
shows:
——
Debugging code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display status
Code
Display status
Code
Display status
02_Allocate
addresses
db
Light
02
Light
oC
Light
Step 8: In progress 03, the quantity of modules needs to be confirmed manually. Main board will
display:
——
Debugging code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display status
Code
Display status
Code
Display status
03_Confirm the
quantity of modules
db
Light
03
Light
Quantity of
modules
Blink
If the quantity displayed is the same with actual quantity, then press SW4 confirmation button on the
master unit to confirm it. Unit will start next progress:
——
Debugging code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display status
Code
Display status
Code
Display status
03_Confirm the
quantity of modules
db
Light
03
Light
oC
Light
If the quantity displayed is different from actual quantity, then disconnect power and check whether
communication wire among each module is correctly connected. After the check, start debugging again.
Step 9: In progress 04, the quantity of IDUs needs to be confirmed manually. Main board will
display:
——
Debugging code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display status
Code
Display status
Code
Display status
04_Confirm the
quantity of IDUs
db
Light
04
Light
Quantity of
connected
IDUs
Blink
If the quantity displayed is the same with actual quantity, then press SW4 confirmation button on the
master unit to confirm it. Unit will start next progress:
——
Debugging code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display status
Code
Display status
Code
Display status
04_Confirm the
quantity of IDUs
db
Light
04
Light
oC
Light
Step 10: Progress 05 is internal communication detection.
If no error is detected, system will display as below and then start next progress.
——
Debugging code
Progress code
Status code
Summary of Contents for Ultra Heat GMV-VQ72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Recovery Series ...
Page 30: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 26 ...
Page 73: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 69 ...
Page 135: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 131 ...
Page 203: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 199 5 4 NCHS4B U ...
Page 205: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 201 5 5 NCHS8B U ...
Page 207: ...Jf00303410 ...