Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial COMMISSIONING OPERATION
88
3.1.1 Outdoor silent mode setting DIP switch (S1)
The outdoor silent mode setting DIP switch (S1) is used to set noise grades at the place needing
low noise, such as hospital, hotel at night, no matter in the daytime or nighttime. The silent modes of unit
include standard mode, low noise mode, medium noise mode, superlow noise mode. The setting
methods are as follows:
Outdoor Silent Mode Setting DIP Switch (S1)
DIP1
DIP2
Noise Range
0
0
Standard mode
1
0
Low noise mode
0
1
medium noise mode
1
1
superlow noise mode
The default factory setting is
―00‖.
On the DIP switch,
―ON‖ indicates ―0‖ status and the opposite direction indicates "1‖ status.
Note that the DIP switch should be independently set on each module.
After silent mode is set, unit
’
s cooling and heating capacity will be lowered correspondingly. Please be
noted.
3.1.2 Outdoor fan static pressure setting DIP switch (S2)
The outdoor fan static pressure setting DIP switch (S2) is used in special scenarios such as the unit
installation equipment room. In scenarios where air ducts are required to be connected, zero static
pressure (0 Pa), low static pressure (30 Pa), medium static pressure (50 Pa), and high static pressure
(82 Pa) can be set according to the design of air ducts. The setting methods are as follows:
Outdoor Fan Static Pressure Setting DIP Switch (S2)
DIP1
DIP2
Static Pressure Range
0
0
0 Pa/0in.W.G.
1
0
30 Pa/0.12in.W.G.
0
1
50 Pa/0.2in.W.G.
1
1
82 Pa/0.328in.W.G.
The default factory setting is
―00‖.
On the DIP switch,
―ON‖ indicates ‖0‖ status and the opposite direction indicates "1‖ status.
Note that the DIP switch should be independently set on each module.
3.1.3 Centralized control address DIP switch (S3)
The centralized control address DIP switch (S3) indicates the centralized control address required
Summary of Contents for Ultra Heat GMV-VQ72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Recovery Series ...
Page 30: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 26 ...
Page 73: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 69 ...
Page 135: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 131 ...
Page 203: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 199 5 4 NCHS4B U ...
Page 205: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 201 5 5 NCHS8B U ...
Page 207: ...Jf00303410 ...