Menus of Inputs/Outputs
continued
CAN 1...10 output Calibrate URZ 40a
1. To calibrate the valve, select the button
from the menu.
2. The current actual value, the hysteresis
and the current properties of the valve Open/
Close. This is shown with arrows on the bar
graphs by a change in colour.
3. The calibration functions are inactive at first
as the valve is not yet switched to manual.
4. When you toggle to manual mode this be-
comes active and the valve can be moved
using Open/Stop/Close.
5. Always identify the current raw value of the
feedback potentiometer. A status report is
also shown in the area below the buttons.
This also contains the end position Open or
Close.
6. When you have moved the valve in the de-
sired direction and reached the end position,
the adjustment can be made and the raw
value that has been reached at that point is
written below the relevant buttons.
Note
When you leave the page, the valve is automatically switched back to manual mode.
A plausibility test is also carried out between the raw values Open/Close.
The difference must be > 100 to achieve the greatest possible accuracy. If this difference
is not achieved, it is shown in red on the screen.