47
Menus of Inputs/Outputs
continued
LRR 140
1. Press the button
LRR 140
in the menu
Current values control equipment
.
2. The current values of the equipment are
shown in the display field.
3. The menu
LRR 140 Setup
is password
protected.
Press
and enter your password.
4. To show the setup menu
press the button
.
Note
The node ID setting in SPECTOR
control
must tally with the node ID setting on the
equipment.
During 72h operation without continuous supervision, the type-tested LRR must be used
as a limiter. Its control and blowdown functions are not supported by the SPECTOR
control
but are implemented by the control circuit of the SPECTOR
control
.
LRR 140 setup
1. Select the menu
LRR 140
.
2. To change or set the node ID, select the green
input field.
3. In the input mask, the on-screen keyboard
can be used to overwrite or change the value.
4. The button
Node On/Off
switches the node ID
to active or inactive.
5. To name the LRR 1-40 select the input field
Name
.
6. In the input mask, the on-screen keyboard
can be used to enter or change the name.
7. The current limit value is shown in yellow.
To change the maximum limit value, select the relevant input field.
8. In the input mask, the on-screen keyboard can be used to enter or change the value.
9. When the limit value is confirmed
the value is sent to the equipment. The value is imme-
diately active.