40
Menus of Inputs/Outputs
continued
Note
The HiHi and LoLo settings can be used for alarms and the Hi and Lo settings can be
used for switchpoints of 2-position controllers and in the menu “Logical links”. It is also
possible to control digital outputs with the limit values entered here.
If all values from HiHi to LoLo are set to 0, limit value monitoring is deactivated.
If HiHi/LoLo alarms are switched off, no entry is made in the alarm log.
Analogue 1...10 input setup
1. In the menu
Analogue 1...10 Input press
.
2. The menu
Analogue Input 1...10 Setup
is
password protected.
Press
and enter your password.
3. To select or change the type of sensor,
press the Type button. The types of input are
shown in a list and can be selected individu-
ally. The selected type must tally with the
components used in the WAGO bus terminal
block.
4. To activate or deactivate the analogue input
press the button
AI On/Off
.
5. To select the unit of the measured value,
select the green input field.
6. Use the on-screen keyboard to enter or modify the value in the input mask.
7. To name the analogue inputs select the input field.
8. In the input mask, the on-screen keyboard can be used to enter or change the name.
9. To change the range values and limit values, select the relevant input field.
First set the ranges 0 % and 100 % and then the limit values.
10. In the input mask, the on-screen keyboard can be used to enter or change the value.