61
Controller Menus
continued
3element continous / 3position controller
1. Press the green button
Parametrised as
in the menu
3element controller
.
2. The menu is password protected.
Press
and enter your password.
3. The values of the steam quantity and the
water flowrate are highlighted in yellow.
Below that, the current level, the status
indicator
Enabled/Disabled
and the
established controller are shown. Next to
these values the setpoint and the current
controller setting are indicated.
4. To change the internal setpoint, select the
green input field.
5. The current value appears in the input
mask. The on-screen keyboard can be used to modify this.
6. Use the arrow buttons to select Automatic mode, Stop, or Manual Mode.
7. If the 3-position controller is in manual mode, a new mask with buttons opens. Use the buttons
to open or close the valve. The selected button is highlighted. If the continuous controller is in
manual mode, the manual manipulated variable is entered into the green input field MANUAL.
8. The controller parameters can be entered for the PID controller in the input fields
P
(Proportional),
I
(Integral) and
D
(Differential).
9. The current value appears in the input mask. The on-screen keyboard can be used to modify this.
10. Below the status display
Enabled/Disabled
and the controller that has been set, the actual value
(X), the calculated level (X1), the setpoint (W), the manipulated value (Yw) and the position feed-
back signal (Yx) are graphically represented as a bar graph.
Note
Only the internal setpoint can be set in this menu.
When the switch position is toggled from Automatic mode to Stop, the current manipu-
lated variable (Yw) of the controller is transferred. This applies for operation as continu-
ous or 3-pos. positioner.
If a position feedback signal is parametrised, the controller functions as a positioner.
If there is no position feedback signal parametrised, or if this sensor is faulty, the control-
ler functions as a 3-pos. stepping controller.
The controllers function as PI controllers.
An I part is a mandatory requirement.