78
4. CONFIGURATION
80703B_MHW_2850T/3850T_02-2019_ENG
4.15.1.3. F-MIX analog output configuration
All the module analog outputs are listed in the upper group,
one per line. Each output is identified by its progressive
number, which corresponds to that shown in the module
wiring diagram (see paragraph “2.7. F-MIX module connec-
tion diagrams” on page 26).
Additional output configuration parameters are shown in the
lower group.
•
F-MIX
: identification number of the module to be con-
figured. It can be selected with the
+
key. In the module
group, the F-MIX modules are numbered progressively,
with the module next to the communication module
assuming number 1.
•
Type
: output type, which is selected by cyclically
pressing the + key. For further information see “10.4.
F-MIX module” on page 150.
•
Name
: the variable name associated with the output.
Touching the field opens the virtual keyboard where
you can enter an identifying name as you like. The
name must be unique for the entire controller and can
be up to 16 characters long, chosen from a ... z, A ... Z,
0 ... 9, and _. This name is used in creating programs
and in logical functions.
The following parameters are used for linear calibration and
conversion of the analogue output value:
•
Eng PV
: resulting engineering unit.
•
Eng min
: minimum engineering unit for calibration.
•
Eng max
: maximum engineering unit for calibration.
•
Ana PV
: points read by the board.
•
Ana min
: minimum number of points for calibration.
•
Ana max
: maximum number of points for calibration.
For further information on calibration conversion, see
paragraph “7.3. Correction of linear inputs and outputs”
on page 107.
•
D.P.
: set the number of decimal places to display the
value in engineering units.
•
[mis]
: unit of measure for values other than tempera-
ture, such as pressure or humidity.
To configure the other module inputs and outputs, tap the
key at the top of the screen.
4.15.1.4. F-MIX digital input configuration
All module digital inputs are listed, one per line. Each input
is identified by its progressive number, which corresponds
to that shown in the module wiring diagram (see paragraph
“2.7. F-MIX module connection diagrams” on page 26).
F-MIX
: identification number of the module to be con-
figured. It can be selected with the
+
key. In the module
group, the F-MIX modules are numbered progressively, with
the module next to the communication module assuming
number 1.
The list contains the names of the variable associated with
the respective input. The default name is
DI_
nn
, where
nn
is a sequential number calculated by the first F-MIX
module (first all F-MIX modules are numbered, then F-EU16
modules). Touching the field opens the virtual keyboard
where you can enter an identifying name as you like. The
name must be unique for the entire controller and can be
up to 16 characters long, chosen from a ... z, A ... Z, 0 ... 9,
and _. This name is used in creating programs and in logical
functions.
Digital inputs do not have parameters to configure.
The current status is displayed on the right, next to the
name (0 = OFF, 1 = ON).
To configure the other module inputs and outputs, tap the
key at the top of the screen.
4.15.1.5. F-MIX digital output configuration
All module digital outputs are listed, one per line. Each
output is identified by its progressive number, which cor-
responds to that shown in the module wiring diagram (see
paragraph “2.7. F-MIX module connection diagrams” on
page 26).
Summary of Contents for 2850T
Page 2: ......
Page 6: ...80703B_MHW_2850T 3850T_02 2019_ENG 4...
Page 10: ...80703B_MHW_2850T 3850T_02 2019_ENG 8...
Page 20: ...80703B_MHW_2850T 3850T_02 2019_ENG 18...
Page 34: ...80703B_MHW_2850T 3850T_02 2019_ENG 32...
Page 104: ...80703B_MHW_2850T 3850T_02 2019_ENG 102...
Page 106: ...80703B_MHW_2850T 3850T_02 2019_ENG 104...
Page 124: ...80703B_MHW_2850T 3850T_02 2019_ENG 122...
Page 128: ...80703B_MHW_2850T 3850T_02 2019_ENG 126...
Page 156: ...80703B_MHW_2850T 3850T_02 2019_ENG 154...