Chapter 4 Software Index
4-52
When PID output frequency is larger than the frequency for sleep start the inverter will be awaked and
enter PID awake mode. The time diagram is as follow:
Parameter Group 13 - Communication mode
13-0
:
:
:
:
Assigned Communication Station Number
:
:
:
:
1 - 254
13-0: to set the communication station codes which are suitable for driving more than one inverters
situations.
13-1
:
:
:
:
Baud Rate setting (bps)
:
:
:
:
0000: 4800
0001: 9600
0002: 19200
0003: 38400
13-2
:
:
:
:
Stop Bit Selection
:
:
:
:
0000: 1 stop bit
0001: 2 stop bit
13-3
:
:
:
:
Parity Selection
:
:
:
:
0000 : no parity
0001 : even parity
0002 : odd parity
13-4
:
:
:
:
Data Format Selection
:
:
:
:
0000 :8 bit data
0001 :7 bit data
1.RS-485 Communication
:
(1)1 vs 1 Controlling
:
to control one inverter by a PC or PLC or controller.(set 13-0 = 1~254)