Chapter 3 Ambient Environment and Installation
3-4
E.
Fuse types
Drive input fuses are provided to disconnect the drive from power in the event that a
component fails in the drive’s power circuitry. The drive’s electronic protection circuitry is
designed to clear drive output short circuits and ground faults without blowing the drive input
fuses. Below table shows the VAT200 input fuse ratings.
To protect the inverter most effectively, use fuses with current-limit function.
RK5, C/T TYPE FUSE FOR VAT200
220V class(1
φ
)
U201N-
HP
KW KVA
100% CONT
Output AMPS (A)
Max.kk5
FUSE Rating(A)
Max.CC or T
FUSE Rating(A)
00K4
0.5
0.4
1.2
3.1
10
20
00K7
1
0.75
1.7
4.5
15
30
01K5
2
1.5
2.9
7.5
20
40
02K2
3
2.2
4.0
10.5
25
50
220v class(3
φ
)
U203N-
HP
KW KVA
100% CONT
Output AMPS (A)
Max.kk5
FUSE Rating(A)
Max.CC or T
FUSE Rating(A)
00K4
0.5
0.4
1.2
3.1
8
10
00K7
1
0.75
1.7
4.5
12
15
01K5
2
1.5
2.9
7.5
15
20
02K2
3
2.2
4.0
10.5
20
30
04K0
5
3.7
6.7
17.5
30
50
05K5
7.5
5.5
9.9
26
50
60
07K5
10
7.5
13.3
35
60
70
440 class(3
φ
)
U203X-
HP
KW KVA
100% CONT
Output AMPS (A)
Max.kk5
FUSE Rating(A)
Max.CC or T
FUSE Rating(A)
00K7
1
0.75
1.7
2.3
6
10
01K5
2
1.5
2.9
3.8
10
15
02K2
3
2.2
4.0
5.2
10
20
04K0
5
3.7
6.7
8.8
20
30
05K5
7.5
5.5
9.9
13
25
35
07K5
10
7.5
13.3
17.5
30
50
11K0
15
11.0
20.6
25
50
60
15K0
20
15.0
27.4
32
60
70
18K5
25
18.5
34.0
40
70
80
22K0
30
22.0
41.0
48
80
100
30K5
40
30.0
54.0
64
100
125
37K0
50
37.0
68.0
80
125
150
45K0
60
45.0
82.0
96
150
200
55K0
75
55.0 110.0
128
200
250
*Fuse ratings are based upon 250V fuses for 230V inverter, and 600V for 460V inverters