Chapter 4 Software Index
4-35
(5) 5-09
≠
0, the inverter will accelerate to the setting of 6-00 and maintain at the speed. When
the UP/Down terminal is On, setting frequency is present value 6-00
±
5-09, and the inverter
will accelerate/ decelerate to frequency 6-00. The upper frequency limit and lower frequency
limit also restrict the operation. If the signal of UP/ DOWN is maintained over 2 seconds, the
inverter will begin to accelerate/ decelerate. If 5-09=0, the operation is the same, till the UP/
DOWN signal stops. Please refer to the time diagram of 5-09.
13.
5-00~06=16 Principal/Auxiliary speed toggle
Multifunction terminal = OFF, the frequency is set by the VR (Master Speed) on the
Keypad. Whereas, Multifunction terminal = ON, the frequency is set by the analog signal
terminal (Auxiliary Speed) on the TM2 on terminal Block.
14.
5-00~06=17(PID Function Disable)
The PID Function Disable is ON. PID is not controlled by 11-0, while OFF, it is controlled
by 11-0.
15.
5-00~06=18(Reset Command)
The Reset command is same as Reset Key on the panel is ON. The command is OFF, and the
inverter does not response. The factory set of 5-05 is Reset command.
16.
5-04=19 (Encoder Input terminal)
The multifunction terminal S5 is set 19 means it is the input terminal for PLC program
Encoder.
17.
5-05=20 (PID feedback input terminal)
The multifunction terminal S6=20 means the PID feedback input terminal and 0~10V (0~
20 mA) or 2~10V (4~20mA)
is available by the setting of 11-0.
18.
5-05=21 /22(Bias signal 1/2 input)
To regulate the Offset of the Keypad VR or AIN analog input, only the signal of 0~10V (0~ 20 mA)
or 2~10V (4~20mA) is available.
Operation
UP
DOWN
Output 6-00
Frequency
Hz
V
10
0
AIN+S6
Hz
V
10
AIN+(S6-5V)
5-05=22Function * The value is 0 when
AIN+(S6-5V)
<
0
0
5
Upper Frequency
Limit 3-00
5-05=21
Function
Upper Frequency
Limit 3-00