Chapter 4 Software Index
4-14
5-08
(Stop Sel by MFIT) Stop Mode Using MFIT
0000: When the MFITs are
Programmed for Up/Down
Frequency Control, the Set
Frequency will remain when
the Drive stops. And when the
Drive stops, Up/Down
Function Disabled.
0001: Up/Down is used.
The preset
frequency is reset to 0 Hz as
the inverter stops.
0002: When the MFITs are
Programmed for Up/Down
Frequency Control, the Set
Frequency will remain when
the Drive stops. And when the
Drive stops, Up/Down
Function Enabled. *7
0000
5-09
(Step Up/Down Fun) Step of Up/Down Function (Hz) 0.00 – 5.00
0.00
5-10
(Pulse Inp. Mult.)
Encoder Inpulse Ratio
0.001 – 9.999
1.000
*7
5-11
(Ref.Source2)
Select the source of auxiliary
frequency command
0 - 4
0
*7
※
Notes: 1. To switch to Run/Stop with Function 1-01 = 0001.
2. To switch to Forward/Reverse with Function 1-01 = 0001.
3. Preset Speed # 3 is obtained by activating Terms. S3 and S4 simultaneously
.
6- Jog, and Preset (MFIT) Frequency Setting on Keypad
Function
Code No.
LCD
Display
Description
Range/Code
Factory
Setting
Remarks
6-00
(Keypad Freq)
Keypad Frequency (Hz)
0.00 - 650.00
5.00
*1
6-01
(Jog Freq)
Jog Frequency (Hz)
0.00 - 650.00
2.00
*1
6-02
(Preset Speed #1)
Preset Speed # 1 (Hz)
0.00 - 650.00
5.00
*1
6-03
(Preset Speed #2)
Preset Speed # 2 (Hz)
0.00 - 650.00
10.00
*1
6-04
(Preset Speed #3)
Preset Speed # 3 (Hz)
0.00 - 650.00
20.00
*1
6-05
(Preset Speed #4)
Preset Speed # 4 (Hz)
0.00 - 650.00
30.00
*1
6-06
(Preset Speed #5)
Preset Speed # 5 (Hz)
0.00 - 650.00
40.00
*1
6-07
(Preset Speed #6)
Preset Speed # 6 (Hz)
0.00 - 650.00
50.00
*1
6-08
(Preset Speed #7)
Preset Speed # 7 (Hz)
0.00 - 650.00
60.00
*1
7- Analog Input Signal Operation
Function
Code No.
LCD
Display
Description
Range/Code
Factory
Setting
Remarks
7-00
(AIN Gain)
AIN Gain (%)
0 - 200
100
*1
7-01
(AIN Offset)
AIN Bias (%)
0 - 100
0
*1
7-02
(AIN Bias)
AIN Bias Selection
0000: Positive
0001: Negative
0000
*1
7-03
(AIN Slope)
AIN Slope
0000: Positive
0001: Negative
0000
*1
7-04
(AIN Scan Time)
AIN Signal Verification Scan
Time (AIN, AI2)
(mSec x 2)
1 - 100
50
7-05
(AI2 Gain)
AI2 Gain (%)(S6)
0 - 200
100
*1