Chapter 4 Software Index
4-33
3.
5-00~06=5(Jog)
To select Jog operation as ON the external input terminals. Now, the inverter operates at the
Jog acceleration and deceleration time. The corresponding frequency parameter is illustrated
below:
The priority order of frequency: Jog Speed
→
Preset Speed
→
Keypad frequency or external frequency
signal
Multifunction
terminal3
Preset value=04
Multifunction
terminal 2
Preset value =03
Multifunction terminal 1
Preset value =02
Jog Command
terminal
Preset value =05
Output frequency
preset value
0
0
0
0
6-00
X
X
X
1
6-01
0
0
1
0
6-02
0
1
0
0
6-03
0
1
1
0
6-04
1
0
0
0
6-05
1
0
1
0
6-06
1
1
0
0
6-07
1
1
1
0
6-08
4.
5-00~06=6 (toggle acceleration and deceleration time)
On the external input terminal, to select the acceleration 1/ deceleration 1/ S curve 1 or
acceleration 2/ deceleration 2/ S curve 2.
5.
5-00~06=7 /29
External Emergency Stop Contact A or B.
The inverter will decelerate to stop and Flash E.S as the emergency stop signal received
regardless of 1-05 setting. After such signal released, OFF the operation switch then ON or Press
Operation Key, the inverter will restart from the start frequency. If the emergency signal was
released before the inverter stop completely, the inverter still carries out emergency stop. The
8-02/03 determines the action of the error terminal. As 8-02/0=0: the error terminal does not act
when the external emergency signal input. While 8-02/03=9, the error terminal does act when
emergency signal input.
6.
5-00~06=8
:
Base Block
The inverter stop output as receiving STOP command, and the motor Free-Run stops.
7.
5-00~06=9
:
Speed Search Stop
When starting, the inverter detects the present speed of the motor firstly, then, the inverter
accelerates from the present speed to preset speed.
8.
5-00~06=10
:
Energy-saving operation
In terms of FAN, PUMP or other heavy inertia loads which need greater start torque, while in
operation they need not so high torsion. Thusly, to decline the output voltage is to saving energy.
The output voltage gradually declines as the multifunction terminal is ON. It will gradually
increase (to the original voltage) as the Multifunction terminal is OFF.
※
Note
:
The acceleration and deceleration speed of energy saving operation is the same as the speed of
SPEED SEARCH.
9.
5-00~06=11
Switch of the control signal
External switch terminal is OFF
:
1-00/01 determines the operation signal and frequency signal.
External switch terminal is ON
:
Keypad controls the operation signal and frequency signal but not