Masoneilan SVI FF Instruction Manual
=
|
183
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
FUNCTION (2)
0-13
0
MAN
OOS
Custom_1_Configuration allows you to select the virtual
switch activation condition.
0. Disabled (always inactive; default).
1. Activates the switch being controlled by the DO
block.
2. Activated when position control in fault state.
3. Activated when position control is not in normal
mode.
4. Activates so the TB reports if maintenance is
required now
5. Activates so the TB reports if maintenance is
required soon.
6. Activated when the air supply is too low.
7. Activated when a Travel Deviation Alert occurs.
8. Activated when a Position HI Alert occurs.
9. Activated when a Position LO Alert occurs.
10. Always active.
11. Always Inactive (same as disabled).
12. Activated when a Reset occurred.
13. Activated when a Tight Cutoff state occurs.
DISCRETE_
SWITCH_2_CONF (83)
MAN
OOS
Discrete switch configuration for switch 2.
Virtual switch.
DIRECTION (1)
MAN
OOS
Value:
1 - Normal Open (default).
0 - Normal Closed.
Table 31 Transducer Block Parameters (Continued)
Parameter (in bold)
Sub-parameter (Index)
Range
Initial
Value
Mode
Description
Summary of Contents for Baker Hughes Masoneilan SVI FF
Page 12: ...This page intentionally left blank ...
Page 72: ...This page intentionally left blank ...
Page 82: ...This page intentionally left blank ...
Page 94: ...This page intentionally left blank ...
Page 108: ...This page intentionally left blank ...
Page 198: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 224: ...This page intentionally left blank ...
Page 228: ...This page intentionally left blank ...
Page 230: ...This page intentionally left blank ...
Page 250: ...This page intentionally left blank ...
Page 262: ...This page intentionally left blank ...
Page 263: ......